WIKA operating instructions temperature transmitter T32.xS
6.3 Configuration
The following parameters can all be configured: sensor model, sensor
connection, user measuring range, output limit, alarm indication,
terminal voltage monitoring, sensor break monitoring, measuring
range monitoring, measuring rate, damping, write protection, offset
values (1-point correction), Tag No. and user linearisation (custom
chararcteristic curve). Furthermore, a linear transformation of the
process value is possible using a 2-point correction.
User linearisation:
Via software, customer-specific sensor characteristics can be stored
in the transmitter in order to define other sensor types. Number of
auxiliary points: min. 2; max. 30. If more than 2 sensors are connected
(dual sensor function) further configurations can be carried out. With
the dual sensor function, two identical sensors (resistance sensor or
thermocouple) with the same measuring range are connected and
then processed together.
The transmitters are delivered with a basic configuration (see data
sheet TE 32.04) or configured according to customer specifications.
If the configuration is changed afterwards, the modifications must be
noted on the label using a water-resistant felt-tip pen.
A simulation of the input value is not required to configure
the T32.
A sensor simulation is only required for the functional test.
6. Commissioning, operation
6.2.2 Transmitter in rail mounting version (model T32.3S)
Fasten the rail mounting case (model T32.3S) onto a 35 mm top-hat
rail (EN 60175) by simply locking it into place without the need for any
tools.
Disassembly is achieved by unlocking the locking element.