WIKA operating instructions, flow switch, model FSM-6100

83790004.00 12/2020 EN

5.3  Mechanical mounting

■ 

Mounting is only permitted in the no flow state. Reliably isolate the line without any 

fluid, using the available valves and protective devices.

■ 

Use seals suitable for the process connection provided.

■ 

When screwing the instruments in, the force required for sealing must not be 

applied through the case, but only through the spanner flats provided for this 

purpose on the process connection and using a suitable tool. The tightening torque 

is dependent on the selected process connection. 

■ 

After screwing in, make sure that no damage or cracks have occurred at the 

process connection.

■ 

Ensure the flow should be along the direction of arrow mark indicated on process 

connection.

■ 

Flow switches should be mounted in horizontal/Vertical section of pipe with a 

minimum straight run of 5 pipe diameter on both upstream and downstream. The 

straight run should be free of bends, valves and other restrictions.

■ 

Drill a 30mm dia hole in pipe. Ensure hole is free of bur and sharp edges, weld 

a 1” BSPT/1”NPT female shank to the pipe, shank height should be maintained 

as 25mm, as shown in the below (fig.2), changing the dimension will result in 

malfunctioning.

5.4  Electrical mounting

The connection cable must provide basic insulation for external circuits of protection 

class I. The instrument must be able to be switched off completely by means of a switch 

or a control unit. Depending on the load, additional protective measures, e.g. for motor 

protection, may be required.

DANGER!

Danger to life caused by electrical current

Upon contact with live parts, there is a direct danger to life

 

The instrument may only be installed and mounted by skilled personnel.

 

Switch off the load circuit before starting work and secure against being 

switched on unauthorised.

Cable preparation

The cable gland used must be suitable for achieving an IP30 ingress protection. Provide 

strain relief for the installed cables. Size the connecting cables for the largest current 

strength in the circuits and ensure sufficient UV resistance and mechanical stability.

Recommendation: 4-wire cable with conductor cross-section of 2 ... 2.5 mm². Wire ends 

fitted with insulated ring lugs suitable for 2 ... 2.5 mm² wire cross section.

Grounding

Include the ground connection in the inside of the instrument into the grounding 

concept of the installation.

Clamping the cable

1.  Remove 2 screws and open the 

cover.  Maximum torque: 1.5Nm

2.  Fit suitable cable gland and route the 

cable via cable gland.

3.  Carry out the terminal assignment 

according to the switching function, 

maximum tightening torque: 2 Nm

4.  Close the cover again and fix it with 

2 supplied screws

Содержание FSM-6100

Страница 1: ...mo CR Italy Tel 39 0372 6404 Fax 39 0372 640490 salesflow it wika com www wika com Flow switch For industrial heat exchangers Model FSM 6100 Contents 1 General information 2 Design and function 3 Safe...

Страница 2: ...all apply Subject to technical modifications Further information Internet address www wika com Relevant data sheet FV 30 10 Abbreviations definitions SPDT Single pole double throw NC Normally closed c...

Страница 3: ...contrary to the intended use 3 3 Improper use WARNING Injuries through improper use Improper use of the instrument can lead to hazardous situations and injuries Refrain from unauthorised modification...

Страница 4: ...ting it down hard Soot vapour dust and corrosive gases Hazardous environments flammable atmospheres Store the instrument in its original packaging in a location that fulfils the conditions listed abov...

Страница 5: ...ectrical mounting The connection cable must provide basic insulation for external circuits of protection class I The instrument must be able to be switched off completely by means of a switch or a con...

Страница 6: ...ken out of operation immediately Ensure that there is no pressure in the instrument and that the load circuit is switched off Protect against being put into operation accidentally Contact the manufact...

Страница 7: ...dismounted instrument in order to protect persons and the environment from exposure to residual media 8 Dismounting return and disposal WARNING Physical injuries and damage to property and the enviro...

Страница 8: ...le combinations ON falling flow LPM ON rising flow LPM Maximum operating flow LPM in mm L mm Mini mum Maxi mum Mini mum Maxi mum 1 25 28 15 50 25 60 150 1 25 32 28 45 100 50 110 150 1 5 40 28 50 140 6...

Отзывы: