WIKA operating instructions, flow switch, model FSM-6100

83790004.00 12/2020 EN

1.  General information

■ 

The mechanical flow switch described in the operating instructions has been 

designed and manufactured using state-of-the-art technology. All components 

are subject to stringent quality and environmental criteria during production. Our 

management systems are certified to ISO 9001.

■ 

These operating instructions contain important information on handling the instru-

ment. Working safely requires that all safety instructions and work instructions are 

observed.

■ 

Observe the relevant local accident prevention regulations and general safety 

regulations for the instrument’s range of use.

■ 

The operating instructions are part of the product and must be kept in the immediate 

vicinity of the flow  measuring instrument and readily accessible to skilled personnel 

at any time.

■ 

Skilled personnel must have carefully read and understood the operating instruc-

tions prior to beginning any work.

■ 

The manufacturer‘s liability is void in the case of any damage caused by using 

the product contrary to its intended use, non-compliance with these operating 

instructions, assignment of insufficiently qualified skilled personnel or unauthorised 

modifications to the instrument.

■ 

The general terms and conditions contained in the sales documentation shall apply.

■ 

Subject to technical modifications.

■ 

Further information:

- Internet address:

www.wika.com

- Relevant data sheet:

FV 30.10

Abbreviations, definitions

SPDT  Single pole double throw
NC

Normally closed contact type (NC = normally closed)

NO

Normally open contact type (NO = normally open)

COM Common contact
GND Ground connection 

2.  Design and function

2.1  Overview

2.2  Description

The flow element of the model FSM-6100 is a paddle which works against a spring 

mechanism with an adjustable pre-load force. On the spring mechanism there is a 

contact arm for actuating the switch contact. The switch is actuated as soon as the force 

generated by the flow is greater than the set pre-load force.

2.3  Terms used

Reset point

The flow value at which the switch returns to the starting position. Mathematically,

the flow value for the reset point is equal to the flow value of the switch point

minus the switch differential on rising flow. On falling flow, the flow value

for the reset point is equal to the flow value of the switch point plus the switch

differential.

Maximum operating flow

The maximum flow with which the instrument can be used without changing the 

assured performance data.

Operating pressure

The maximum pressure with which the instrument can be used without changing the 

assured performance data.

With stand pressure

The maximum pressure with which the instrument can hold without any damage to the 

system and surroundings.

2.4  Scope of delivery

Flow switch, operating instructions

Cross-check scope of delivery with delivery note.

Содержание FSM-6100

Страница 1: ...mo CR Italy Tel 39 0372 6404 Fax 39 0372 640490 salesflow it wika com www wika com Flow switch For industrial heat exchangers Model FSM 6100 Contents 1 General information 2 Design and function 3 Safe...

Страница 2: ...all apply Subject to technical modifications Further information Internet address www wika com Relevant data sheet FV 30 10 Abbreviations definitions SPDT Single pole double throw NC Normally closed c...

Страница 3: ...contrary to the intended use 3 3 Improper use WARNING Injuries through improper use Improper use of the instrument can lead to hazardous situations and injuries Refrain from unauthorised modification...

Страница 4: ...ting it down hard Soot vapour dust and corrosive gases Hazardous environments flammable atmospheres Store the instrument in its original packaging in a location that fulfils the conditions listed abov...

Страница 5: ...ectrical mounting The connection cable must provide basic insulation for external circuits of protection class I The instrument must be able to be switched off completely by means of a switch or a con...

Страница 6: ...ken out of operation immediately Ensure that there is no pressure in the instrument and that the load circuit is switched off Protect against being put into operation accidentally Contact the manufact...

Страница 7: ...dismounted instrument in order to protect persons and the environment from exposure to residual media 8 Dismounting return and disposal WARNING Physical injuries and damage to property and the enviro...

Страница 8: ...le combinations ON falling flow LPM ON rising flow LPM Maximum operating flow LPM in mm L mm Mini mum Maxi mum Mini mum Maxi mum 1 25 28 15 50 25 60 150 1 25 32 28 45 100 50 110 150 1 5 40 28 50 140 6...

Отзывы: