6. Faults
Warnings and errors
Via the digital display, the instrument's internal errors are displayed. The following table shows the error codes and their
meaning.
WARNING
Description
ATT1
On changing the switch point, the reset point of the instrument is automatically reduced
ATT2
Trim function cannot be executed because a parameter is outside the permissible limits
■
For flow unit %: Smallest span for teach function not maintained
■
For flow units other than %: Offset or correction factor is outside the permissible limit
ATT3
Password entered for menu access is incorrect
ATT4
The entire measuring range cannot be displayed. DiOL (“display overload”) is shown outside the display range
ATT5
Maximum turndown exceeded
ILOC
Menu locked over IO-Link
SC
Short circuit of output 1 or/and output 2
PAS
Prompt for password input
OL
Overload, measuring range exceeded > approx. 25 % (display blinks)
Error
Description
ERR
General error
■
Reset to factory setting
■
Restart the instrument
ERR1
Ambient conditions outside the specification
■
Supply voltage too low
■
Internal temperature at display too high
ERR2
Sensor error
Acknowledgement of an error display by pressing the "Enter" key.
Содержание FSD-4
Страница 68: ...14399527 01 05 2021 EN DE FR ES 68 WIKA operating instructions flow switch model FSD 4...
Страница 104: ...14399527 01 05 2021 EN DE FR ES 104 WIKA mode d emploi pour le capteur de d bit type FSD 4 FR...
Страница 138: ...14399527 01 05 2021 EN DE FR ES 138 WIKA operating instructions flow switch model FSD 4...
Страница 139: ...14399527 01 05 2021 EN DE FR ES 139 WIKA operating instructions flow switch model FSD 4...