14399527.01 05/2021 EN/DE/FR/ES
16
WIKA operating instructions flow switch, model FSD-4
EN
5.5 Overview of parameters
Menu
item
Description
Parameter
Factory
setting
INI
Initialisation menu
-
-
UNIF
Flow unit
m/s, l/min, m3/h(m³/h), FT/s, FT3m (ft³/s),
UGPm (US Gal/min), GPm (Imp. Gal/min), %
m/s
TIF
Min / Max flow setting, only active with UNIF = %
MIN (NO/YES) sets current flow value to 0 %
MAX (NO/YES) sets current flow value to 100 %
-
0SET
Zero point setting /“Autozero” version, only active
when UNIF ≠ %
YES/NO
YES sets current flow value to zero
-
mu_F
Flow multiplier, only active when UNIF ≠ %
0.10 … 10.00
1.00
uniT
Temperature unit
°C, °F
°C
PIPD
Pipeline diameter in mm, only active when UNIF ≠ %
10 … 1,000
25
SP1 / SP2
Hysteresis function: Switch point (switching output 1
if applicable 2)
0.05 … 3 m/s [0.17... 9.84 ft/s]
1.7 … 100 %
If SP2 is configured for temperature:
-18.2 ... +85 °C [-0.8 ... +185 °F]
3.000 (m/s)
FH1 / FH2
Window function
Window high (switching output 1, if applicable 2)
-
-
RP1 / RP2
Hysteresis function: Reset point (switching output 1,
if applicable 2)
0 … 2.950 m/s [0 ... 9.67 ft/s]
0 … 98.3 %
If SP2 is configured for temperature:
-20 ... +78.2 °C [-4 ... +172.8 °F]
2.700 (m/s)
FL1 / FL2
Window function
Window low (switching output 1, if applicable 2)
-
-
EF
Extended programming functions
-
-
RES
Reset the parameters to factory setting
YES/NO
-
DS1 /
DS2
Switching delay time, which must occur without
interruption before any electrical signal change occurs
(SP1, if applicable SP2)
0.00 ... 65.00 s
0.00 s
5. Commissioning, operation
Содержание FSD-4
Страница 68: ...14399527 01 05 2021 EN DE FR ES 68 WIKA operating instructions flow switch model FSD 4...
Страница 104: ...14399527 01 05 2021 EN DE FR ES 104 WIKA mode d emploi pour le capteur de d bit type FSD 4 FR...
Страница 138: ...14399527 01 05 2021 EN DE FR ES 138 WIKA operating instructions flow switch model FSD 4...
Страница 139: ...14399527 01 05 2021 EN DE FR ES 139 WIKA operating instructions flow switch model FSD 4...