21
WIKA operating instructions model A2G-200
20210728.01 10/2021 EN/DE
EN
Register Parameter description
Data type Value
Range
4x0007
T low limit
16 bit
0…450
0 … 45.0 °C
4x0008
Parameter for relay
0…3
0 = CO₂, 1 = r. h.,
2 = T, (3 = Off)
4x0009
CO₂ relay on
500…1950
500 … 1,950 ppm
4x0010
CO₂ relay off
450…1900
450 … 1,900 ppm
4x0011
R. h. relay on
15…990
1.5 … 99.0 %
4x0012
R. h. relay off
10…985
1.0 … 98.5 %
4x0013
T relay on
15…490
1.5 … 49.0 °C
4x0014
T relay off
10…485
1.0 … 48.5 °C
Function code 04 - Read input registers
Register Parameter description
Data type Value
Range
3x0001
Parameter for analogue
output
16 bit
0…3
0 = CO2, 1 = r.F.,
2 = T, 3 = MAX
3x0002
CO₂ reading
0…2000
0 … 2,000 ppm
3x0003
R. h. reading
0…1000
0.0 … 100.0 %
3x0004
T reading
0…500
0.0 … 50.0 °C
3x0005
CO₂ high limit
500…2000
500 … 2,000 ppm
3x0006
CO₂ low limit
0…1900
0 … 1,900 ppm
3x0007
R. h. high limit
100…1000
10.0 … 100.0 %
3x0008
R. h. low limit
0…900
0.0 … 90.0 %
3x0009
T high limit
50…500
5.0 … 50.0 °C
3x0010
T low limit
0…450
0 … 45.0 °C
3x0011
Parameter for relay
0…3
0 = CO₂, 1 = r. h.,
2 = T, (3 = Off)
3x0012
CO₂ relay on
500…1950
500 … 1,950 ppm
3x0013
CO₂ relay off
450…1900
450 … 1,900 ppm
3x0014
R. h. relay on
15…990
1.5 … 99.0 %
3x0015
R. h. relay off
10…985
1.0 … 98.5 %
3x0016
T relay on
15…490
1.5 … 49.0 °C
3x0017
T relay off
10…485
1.0 … 48.5 °C
5. Commissioning, operation