Instruction manual (translation from original) 

flare

 TIME FM6-2 230 V                         

81.020.0025.0 

 
 
Multifunction time relais 

Wieland Electric GmbH 
Brennerstraße 10-14 
96052 Bamberg 
Tel.:  +49 (951) 9324-0 
Fax:  +49 (951) 9324-198 
Internet: www.wieland-electric.com 
Email: [email protected] 

 

 

Doc. # 

BA001111

 - 01/2017 (Rev. A) 

flare TIME FM6-2 230 V 

 

EN

 

 

 

 

 

 

N O T I C E  

Personnel which installs, programs, operates or maintains this device must have read and 
understand these instructions. 

 

W A RN I N G 

 

The personnel must be thoroughly familiar with all warnings, notes and procedures de-
scribed in these operating instructions. 

 

Where necessary, safety precautions and safety devices must comply with the applicable 
regulations. 

 

Damaged products must neither be installed nor put into operation. In case of a defect, 
please return the device to Wieland Electric. 

 

Connect or disconnect only when de-energized! 

 

The device may not be opened. 

 

Do not introduce any objects into the unit! 

 

Keep away from fire and water! 

1

 

Figure 1: Controls and functional components, LEDs 

flare TIME FM6-2 

Front 

 

Back 

 

Front 

1.: LED Actual time display 
2.: LED Target time display 
3.: LED hh:mm  
(green, mode active) 
4.: LED mm:ss  
(green, mode active) 
5.: LED state time contact 
(red, active) 
6. Rotary knob for time and 
time range, press to 
confirm 

 

Back 
1.  K1 time contact 
2.  K2 time contact / 

instant contact 

3.  X1 Supply voltage 
4.  Settings: configu-

ration via DIP-
switch 

5.  X2 external 

2

 

Dimensions and sheet metal cut-out 

  

 

 

   

 

3

 

Connection assignment and DIP configuration 

 

K1: Relay output with change-over contact 
K2: Relay output with change-over contact 
X1: supply voltage 
X2: External control inputs 
Settings: DIP-switch configuration 

DIP-Konfiguration 

DIP  ON 

OFF 

Configuration instant contact 

 

 

K2 = instant contact 

 

 

K2 = time contact 

 

Bit1  Bit2  Bit3  Configuration time function 

 

 

 

Delay-on energization 

 

 

 

Release-delay 

 

 

 

Single shot 

 

 

 

Single shot falling edge 

 

 

 

clock generator break starting 

 

 

 

clock generator impulse 
starting 

 

DIP  ON  OFF 

Configuration Remanence 

 

 

Save time configuration 

 

  Do not save time configuration 

 

DIP  ON  OFF 

Konfiguration der Zeitbasis 

 

 

Time base conversion via rotary 
knob programming 

 

  Time base conversion via control 

input (X2) 

Default: mm:ss 

 

N O T E  

 

Switch off power supply (contacts A1/A3) before changing the configuration via DIP-
switches 1 - 6. 

 

If an invalid DIP-configuration is chosen, the LED-digits on the front display are flashing 
red. All digits show the number '8'.  

4

 

Setting the parameters via the rotary knob 

 
 
 
 
 
 
 
 
 
 
 
 
Configuring the target time – 'time configuration' mode 
The target time for all time functions is universally configured using the rotary knob on the 
front side.  
To switch to 'time configuration' mode:  
1.

 

Press the rotary knob for longer than three seconds (but shorter than five seconds). The 
LED display 2 then shows the currently valid time (static), while LED display 1 shows the 
new, modified (if applicable) time in a flashing rhythm of 2 Hz.  

2.

 

Adjust time by turning the rotary knob. Turning the knob clockwise = increase the time, 
turning the knob anti-clockwise = decrease the time. The amount of the increase or de-
crease depends on the configured time range: 
time range 'hh:mm':  raising or reducing by 1 minute 
time range 'mm:ss' :  raising or reducing by 1 second 

3.

 

To accept the modified time, press the rotary knob within ten seconds of the last 
change. The change is accepted and the device returns to normal mode. The LED dis-
play 1 stops flashing and the two time displays now show the same value. 
If no action occurs on the rotary knob within ten seconds (timeout), any changes made 
are discarded and the most recent valid time is retained. The upper display stops flashing 
 

N O T E  

To retain the modified time after a power failure, the DIP switch DIP5 must be set to 'on' 
(remanence, save time). 

 

If DIP5 is in the 'off' position (do not save time), the target time is preset to '00:00' when 
the power supply returns and must then be reconfigured. 

 
Configuring the time base - 'time range configuration' mode (only when DIP6 ='on') 
In 'time range configuration' mode, the time range can be switched from 'hh:mm' to 
'mm:ss' and vice versa.  
1.

 

Press the rotary knob for at least five seconds to switch to “time range configuration” 
mode. 
The two green LEDs of the time ranges 'hh:mm' and 'mm:ss' flash alternately with 2 Hz.  

2.

 

Turning the rotary knob selects the required time range.  
The LED of the selected time range will then stay lit. 

3.

 

Press the rotary knob within ten seconds of the last change to accept the selected 
time range.  
The device returns to normal mode. Be aware that when accepting the modified time 
range the target time is set to 00:00 and must be reconfigured. 
If no action occurs on the rotary knob within ten seconds (timeout), any changes made are 
discarded and the device returns to normal mode. In this case, the settings for the time 
range and target time that were valid before activating 'time range configuration' mode 
are retained 

N O T E  

The following applies for both 'time configuration' and 'time range configuration' mode: 
The time and time base can only be configured when a time sequence is inactive. If a time 
sequence is active or paused, operating the rotary button has no effect.  
If the modification of the time and/or time range is necessary, the time sequence must be 
stopped, e.g. by activating the stop/reset input. 

5

 

START- / STOP-functions 

 

A1/A2: The supply voltage (contacts A1-A2) must be present in order to be able to activate 
switching functions. 

 

An addition voltage to X2 controls the start (Pin1/2) and stop (Pin3/4) function. 

 

If time contact K1 is in the operating position, the red status LED lights up (5). 

 

After the chosen time has run out, the display flashes in a rythm of 2 Hz. 

 


standard 

mode 

 

mode  

'time configuration' 

 

press button 

3 s 

 

mode 'time range 

configuration' 

 

press button 

5 s 

 

timeout 10 s: => 

without saving 

press button => 

save new value 

press button => 

save new value 

timeout 10 s: => 

without saving 

Содержание flare TIME FM6-2 230 V

Страница 1: ... gegen den Uhrzeigersinn Verminderung Zeitwert Die Erhöhung bzw Erniedrigung ist jeweils abhängig vom eingestellten Zeitbereich Zeitbereich hh mm Erhöhung bzw Erniedrigung um 1 Minute Zeitbereich mm ss Erhöhung bzw Erniedrigung um 1 Sekunde 3 Durch drücken des Drehknopfs innerhalb von 10 Sekunden nach der letzten Veränderung wird die Zeit übernommen Die Änderung wird übernommen und das Gerät schal...

Страница 2: ...gang auf EIN ist startet der Zeitablauf Wechselt der Stop Reset Eingang auf EIN schalten der Zeitkontakt und der Sofortkontakt AUS Hinweis Der Zeitausgang schaltet nicht wenn die Zeiteinstellung 00 00 ist Technische Daten Versorgung X1 A1 A2 Spannungsbereich 90 265 V AC DC Versorgungsspannung Frequenz AC 50 60 Hz Bemessungsleistungsaufnahme 2 W Steuereingänge X2 Spannungsbereich 20 4 256 V AC DC B...

Страница 3: ...ed if applicable time in a flashing rhythm of 2 Hz 2 Adjust time by turning the rotary knob Turning the knob clockwise increase the time turning the knob anti clockwise decrease the time The amount of the increase or de crease depends on the configured time range time range hh mm raising or reducing by 1 minute time range mm ss raising or reducing by 1 second 3 To accept the modified time press th...

Страница 4: ...If the stop reset input changes to ON the time contact and the instant contact switch to OFF Note The time output doesn t switch if time is set to 00 00 Technische Daten Power supply X1 A1 A2 Voltage range 90 265 V AC DC Supply voltage frequency AC 50 60 Hz Rated consumption 2 W Control inputs X2 Voltage range 20 4 256 V AC DC Rated frequency AC 50 60 Hz Rated current 2 mA Min impulse duration 100...

Отзывы: