flare TIME FM6-2 230 V
EN
Explanation of switching functions:
Time function AV (Bit1-3: off-off-on): response-delay
The time sequence starts if START-input switches to ON, and is being reset if START-input
switches to OFF. After switching off the power supply the START-input must change to ON
to restart the time sequence. If the STOP-/RESET-input changes to ON the time contact and
the instant-contact switch to OFF.
Note: The time output doesn't switch if time is set to 00:00.
Time function RV (Bit1-3: off-on-off): release-delay
The output switches to ON if the start-signal-input switches to ON (except the stop-/reset-input
is ON). After the time sequence has expired the output switches to OFF. After switching off the
power supply the start-input must change to ON to restart the time sequence. If the stop-/ reset-
input changes to ON the time contact and the instant-contact switch to OFF.
Note: The time output doesn't switch if time is set to 00:00.
Time function EW (Bit1-3: off-on-on): Single shot
If start-input switches to ON, the output switches to ON and the time sequence starts. After
the time sequence has expired the time delay is reset and the output switches to OFF. If the
start-input switches to OFF while the time sequence is running, the time output switches to
OFF. After switching off the power supply the start-input must change to ON to restart the time
sequence. If the stop-/reset-input changes to ON the time contact and the instant-contact switch
to OFF.
Note: The time output doesn't switch if time is set to 00:00.
Time function AW (Bit1-3: on-off-on): Single shot falling edge
Output switches to ON and the time sequence starts, if the start-input switches to OFF. After
the time sequence has expired the time delay is reset and the output switches to OFF. If the
start-input switches to ON and to OFF again while the time sequence is running, the time
output stays ON. The time sequence is not restarted. After switching off the power supply the
start-input must first change to ON and then to OFF again to restart the time sequence. If the
stop-/reset-input changes to ON the time contact and the instant-contact switch to OFF.
Note: The time output doesn't switch if time is set to 00:00.
Time function TP (Bit1-3: on-on-off): clock generator break starting
The time sequence starts if start-input switches to ON. At the beginning the time contact is OFF.
The output is inverted every time after the time sequence has expired. As long as the start-input
is ON the time sequence starts. If the stop-/reset-input changes to ON the time contact and the
instant-contact switch to OFF.
Note: The time output doesn't switch if time is set to 00:00.
Zeitfunktion TI (Bit1-3: on-on-on): Taktgeber mit Impuls beginnend
The time sequence starts if the start-input switches to ON. In the beginning the time contact
is ON. The output is inverted every time after the time sequence has expired. As long as the
start-input is ON the time sequence starts. If the stop-/reset-input changes to ON the time
contact and the instant-contact switch to OFF.
Note: The time output doesn't switch if time is set to 00:00.
Technische Daten
Power supply (X1:A1-A2)
Voltage range
90…265 V AC/DC
Supply voltage frequency AC
50/60 Hz
Rated consumption
2 W
Control inputs (X2)
Voltage range
20,4… 256 V AC/DC
Rated frequency AC
50/60 Hz
Rated current
<2 mA
Min. impulse duration
100 ms
Min. duration between two status
changes of the control input
500 ms
Input functions
Start; Stop-/Reset; time range change-over
Output / Switching contact(K1, K2)
Contacts
2 change-over contacts, potential-free
Contact usage (parameterized via
DIP-switch)
2 time contacts or 1 time contact (K1) + 1 instant contact
(K2)
Rated voltage
250 V AC 24 V DC
Max. thermal current (ohmic load)
5 A, 250 V AC / 30 V DC
AC15: 250 V / 1,5 A
DC13: 24 V / 0,5 A
Min. switching load
5 V AC / DC, 100 mA ohmsch
Mechanical life time
10 x 10
6
switching cycles
Electrical life time
100 x 10
3
switching cycles
Contact material
AgSnO
2
Time ranges / Operating modes
Time range (2 time ranges)
1 s … 59 min 59 s
1 min … 99 h 59 min
Repeat accuracy
± 0,05 % ± 50 ms
Operation modes / time functions
(6 functions)
AV:
ON delay
RV:
Release delay
EW:
Single shot
AW: Single shot falling edge
TP:
C
lock generator break starting
TI:
C
lock generator impulse starting
Function display
A – LED-time display 1
B – LED-time display 2
C – Time range display (LED)
D – Status display (LED)
Four-figure number display, elapsed time, color: red
Four-figure number display, target time, color: red
Time range ‚hh:mm‘ or ‚mm:ss‘ (LED green)
Status time output (LED red)
Isolation properties
Isolation voltage (input / output)
2.000 V AC (50 / 60 Hz, for 1 min)
Isolation resistance (A1, A2 / contacts) Min. 100 MΩ bei 500 V DC
Pollution degree /
overvoltage category
2 / III
Operation / dimensions / connectors
Operating temperature [T
U
]
-25 …. +60 °C
Storage temperature [T
UL
]
-40 … +70 °C
Operating humidity
25 … x85 %
RH
Dimensions front (B x H)
72 x 72 cm
Mounting
Front panel mounting (DIN IEC 61554)
Mounting of the housing
Screw terminal block
Installation size / front panel hole (B x
H)
68 x 68 mm (depth 63 mm, without plug-connector)
Weight
App. 210 g
Housing material, housing color
Plastic, black (RAL9005)
Fire behaviour of housing
UL94 V0
Protection class
Front IP54 back IP20
Terminal block power supply (X1)
Screw terminal block
Terminal block control inputs (X2),
relay outputs
Spring-loaded terminal blocks
Spring clamps (X1):
Connector cross-section (ein-
/feindrähtig)
Abisolierlänge
Empfohlenes Drehmoment
min. 0,14 mm² (AWG22), max. 2,5 mm² (AWG12)
6 mm
0,5 - 0,6 Nm
Federkraftklemmen (K1, K2, X2)
Anschlussquerschnitt (solid-/fine-
stranded)
Conductor strip length
min. 0,2 mm² (AWG22), max. 1,5 mm² (AWG16)
6 mm
Connector-/ terminal assignment (s. fig. 1 Controls and functional components)
X1
A1, A2 Supply
Supply voltage (U
I_N
)
X2
1, 2
START
Control input 'START'
X2
3, 4
STOP-/RESET
Control input 'STOP-/RESET'
X2
5, 6
TIMEBASE
Control input 'TIMEBASE'
K1
Switching contact (switch output, relay contacts 15, 16, 18)
K2
Switching contact (switch output, configurable with DIP1
as a time contact (relay contacts 25, 26, 28) or as instant
contact (relay contacts 21, 22, 24)
Approvals and norms
CE
EN61812-1:2012
EMV 2004/108/EC;
Low-Voltage Directive 2006/95/EC