WhisperGen PPS16 Installation and Commissioning Manual Rev: 080801
29
14.
WhisperGen check
To check the WhisperGen before commissioning:
1. Remove the enclosure cover and ensure that:
•
spare parts, tools and the User’s Manual are present;
•
there is no damage to the WhisperGen engine;
•
the burner is correctly positioned; and
•
the red silicon rubber burner seal, and springs are in place.
If the WhisperGen is damaged, or parts are missing, contact the WhisperGen distributor.
2. Ensure that the WhisperGen has been pressurised with nitrogen gas.
See page 4
Pressurising the WhisperGen,
in the Installation section of this manual.
3. Ensure that the exhaust heat exchanger has been bolted to the burner.
See page 5 in the Installation section of this manual.
15. Monitoring the WhisperGen using the
Control Panel.
Warning:
If Auto restart is set to >0, the WhisperGen may attempt to restart automatically
After a fault.
See the WhisperGen User’s Manual for control panel operation.
The WhisperGen control system monitors the starting, and running phase of the WhisperGen by
checking the values given by the sensors.
If the microprocessor finds that sensor values are outside a specific range, (set in the
WhisperGen control program), then the WhisperGen produces a warning or fault, and in some
cases it is shut down.
To restart the WhisperGen after it has automatically shut down:
•
If the cause of the shutdown is known, fix the fault, and clear the fault from the screen.
Fault odes and suggested fixes are given in the WhisperGen User’s Manual.
•
try to restart the WhisperGen. The WhisperGen must complete its cooldown routine
before a restart.