ASTER

 F

ILE

 E

NTRY

4-21

Tenant

.    Optional  (

zoom

  available).    Enter  a  four-digit  maximum  tenant  code  number.

Default is 0.

Computer ID.

  Required.  Enter the ID of the computer on which this poller is to run.  Default

is 0—host computer.

 

Poller Number

.  Required.  Enter the number of the corresponding poller-parameter file.

Refer to the configuration sheet detailing the factory-assigned poller numbers.

5

Poller Type

.  Required.  Use the zoom feature (F7) to access the Poller Type Display

 

screen.

Once there, arrow down to the required poller type, press F1, and the poller type number is

entered automatically into the 

Poller Entry

 screen.

6

Disable

.  Not currently implemented.

7

Zone Number

.  Required.  Enter a four-digit maximum zone number.  Default is 0.

D

EVICES

The most common devices used with SE 6000 system are the WSE NexSentry, 708P, 8

xx

-

series and 422 ACUs.  Other devices supported include:

Opto 22 input / output controllers

CCTV switchers

Radionics alarm panels

One or more additional SE 6000 systems used as local controllers

With the exception of the NexSentry, 8

xx

-series and 422 ACUs, each individual device type

requires its own poller and associated hardware port assignment.

S

IMPLE

 / I

NTELLIGENT

 D

EVICE

 T

YPES

The  terms 

simple

  and 

intelligent

  are  often  used  to  describe  certain  device  types  used  in

conjunction with the SE 6000.

Simple  Devices

.    With  simple  devices,  the  SE  6000  makes  the  access  decisions  and  also

instructs the device to take various actions.  The 708P ACU is a simple device, for example.

Intelligent Devices

.  Depending on system configuration requirements, intelligent devices can

be programmed to make their own decisions concerning access and actions to be taken.  The

devices typically have their own application software and / or firmware, and they maintain their own

internal data files which are used for decision making.  The NexSentry, 8

xx

-series, and 422 ACUs

are intelligent devices, for example.  As required, the intelligent devices can be set up to be

Содержание SE 6000

Страница 1: ...ecurity Electronics an ISO 9001 certified company 5452 Betsy Ross Drive SantaClara CA95054 1184 408 727 5170 FAX 408 727 6707 P N 66107919001 Rev F STANDARD PRODUCT MANUAL SECURITY MANAGEMENT SYSTEM S...

Страница 2: ...repair or replace free of charge the equipment found upon WSE s inspection to be so defective or if agreed upon refund the purchase price less a reasonable allowance for depreciation in exchange for t...

Страница 3: ...reens 1 13 FINDING ADDING AND STORING DATA 1 13 Finding Data 1 13 Searching With Partial Information 1 13 Adding Changing Data 1 14 Storing Data 1 14 DELETING RECORDS 1 14 ZOOM FEATURE 1 15 Cancel Zoo...

Страница 4: ...EPORTS 3 1 INTRODUCTION 3 1 POINT HISTORY REPORT 3 2 Point History Sample Report 3 2 KEYHOLDER HISTORY REPORT 3 2 Keyholder History Sample Report 3 3 TRANSACTION HISTORY REPORT 3 3 Transaction History...

Страница 5: ...Device Entry dev_entr All Device Types 4 22 SE NexSentry Device Configuration Entry nexsentr 4 26 Readers 4 31 Reader Entry rdr_entr 4 32 Points pnt_entr 4 39 Auto Opens Activates 4 42 Device Report...

Страница 6: ...TION REPORTS 5 13 Zones 5 13 Zones Sample Report 5 14 Pollers 5 14 Pollers Sample Report 5 14 Devices 5 14 Devices Sample Report 5 15 Readers 5 15 Readers Sample Report 5 16 Points 5 16 Points Sample...

Страница 7: ...12 Transactions tranentr 6 12 DATABASE MAINTENANCE DB_MENU 6 14 Display Database Statistics dbstats 6 14 Perform Backup bkup 6 14 Alarm Transaction Clean Up alrmcln 6 16 Journal Archive jourarch 6 16...

Страница 8: ...rking Stickers items merged into the System Administration section Section 2 Monitor Security Activity Section 3 Security Management Reports Section 4 Master File Entry Section 5 Master File Reports S...

Страница 9: ...for distributed processing or they can be associated with the host computer for central processing Access Group A group of access codes created to facilitate the assignment of similar access privileg...

Страница 10: ...instructionsorcontrolsmaybeassigned seeAccessControlFunctionsinthissection System Hardware Devices The principal device is the host computer The host controls all data maintained in the database recor...

Страница 11: ...or switches The computer controls only the lock power to the door and the door switches are the contact points which inform the computer whether a specific door is open or closed Each door switch is a...

Страница 12: ...not required although Hewlett Packard computers are preferred because of performance and worldwide service Application programs run under an SCO UNIX operating system Installation Flexibility The SE 6...

Страница 13: ...mmunications Monitor Permits security personnel to check all wiring and communications to all hardware elements and displays raw data exchange between the host computer and a connected device Event Mo...

Страница 14: ...em printer AlarmsandResponses Ahistoryreportofalarmswhichoccurredataspecifictimeandlocation and the responses taken by the security staff All Transactions A report detailing all system activity The it...

Страница 15: ...n and other poller specific information Becauseallsystemactivityisbasedonfour digitIDnumbers youneedtodecidebeforedataentry howthesenumbersaretobeassignedtothesystemhardwareelements Althoughthenumberi...

Страница 16: ...5 Maps 23 System Owner Name 8 Access Codes 16 Transactions 24 Terminals for Alarm Auto Switch NOTE Consult the system installer if you have questions concerning numbering In any case keep track of you...

Страница 17: ...Enter Selection field The highlight bar controlled by the arrow keys is used to make a selection to be placed into the Enter Selection field Screen access descriptions are given in Moving Between Scr...

Страница 18: ...se video Indicates if the zoom feature exists for a field see Zoom Feature in this section Displays the number of records found as a result of a find request see Finding Adding and Storing Data in thi...

Страница 19: ...ce and press F2 to display the selection 3 Press Enter anywhere in the list of choices to move the highlight bar to the Enter Selection field Press Ctrl y to clear the field and type the title of the...

Страница 20: ...s Enter to advance the highlight bar until you reach the second search item Issue Date andtype05 01 96 Note Enterthedateaccordingtotheformatforyoursystem thatis either MM DD YY or DD MM YY 4 Press F3...

Страница 21: ...rmation all the new data is lost DELETING RECORDS From time to time it may be necessary to delete records from the database The delete record function is easy to perform although some cautions are inv...

Страница 22: ...e screen press Enter to let the computer know you ve read the message The computer will not allow further action and will beep each time you press a key until you press Enter to acknowledge Occasional...

Страница 23: ...he last message displayed when the internal shutdown procedures have completed is Safe to Power Off or Press any Key to Reboot It is now safe to power off the computer To restart the computer press an...

Страница 24: ...r File Reports Key Inventory Parking Stickers System Administration Appendix B System Screen Hierarchies Appendix B lists all screens within their respective tree structures along with a brief explana...

Страница 25: ...g lot attendant activity and keeps track of the number of cars in the lot on a tenant by tenant basis Remote Dial Up Interface RDI Permits communication with remotely located 8xx series devices via di...

Страница 26: ...ted as transactions any system event occur Most monitor screens are divided this way and for user convenience the screen examples from this point on are shown without the transaction listings Also oth...

Страница 27: ...data item to be controlled then press the applicable function key for the system action to be taken CONTROL FUNCTIONS MENU Pollers The Control Pollers screen displays point ID description status Contr...

Страница 28: ...Devices The Control Devices screen displays point ID description status tamper shunt Applies to NexSentry 422 and 8xx series ACUs Control Devices Function Keys F2 DEV STAT DeviceStatus WhenF2ispressed...

Страница 29: ...Locks The Control Locks screen displays point ID description lock status shunt sensor coax door status Control Locks Function Keys F2 LOCK Lock selected door If no door is selected F2 locks all doors...

Страница 30: ...ted input point previously shunted If no input point is selected F6 unshunts all input points in the zone Output Points The Control Outputs screen displays point ID description status shunt Control Ou...

Страница 31: ...he zone F6 UNSHUNT Unshunt a selected door previously shunted If no door is selected F6 unshunts all doors in the zone Select Zone The Select Zone screen displays zone description count PBarea PBtype...

Страница 32: ...s correct but the passback zone report which reads the keyholder file does not include the locked records F3 corrects the zone count where privileged keyholders not subject to passback control have re...

Страница 33: ...ered F3 INSTRUCT Instructions Press F3 to display a list of actions to take in response to the alarm F4 RESPONSE Press F4 to display the alarm response entry screen First enter Y or N in the situation...

Страница 34: ...which directly affects keyholder access Control Projects Function Keys F2 ACTIVATE Activates a project F3 DE ACTIV Deactivates a project F4 NORMAL Normalizes a project based on start stop dates and t...

Страница 35: ...ol The system handles vehicle and personal passback separately To allow the keyholder to enter the area use the forgive passback function 1 Enter key number or ALL for all keyholders press Enter 2 Pre...

Страница 36: ...all device F3 HANGUP Disengage connection Building Modes Building modes open closed limited combined with the ACU report definitions provide an extra level of security when the building is empty or a...

Страница 37: ...isk Almost Full Warning This feature warns operators when the disk drive has reached a specified percentage of its total capacity Whenthewarningappears takeimmediateactiontoreducetheamountofdatastored...

Страница 38: ...y the monitor program at log on time and remains in effect as long as the monitor program is active A change to the Timeout value does not take effect until the user logs off and then logs back on to...

Страница 39: ...eges consistent with their own custom security profiles This feature uses the PASSWORD keyword parameter located in the DATAPATH MONITOR file The acceptable values are PASSWORD keyword missing Feature...

Страница 40: ...that generate log messages are logged with the user ID entered to gain access to the requested function 4 Permissions associated with the entered login ID remain in effect until the operator returns...

Страница 41: ...following displays and reports Monitor screen both full and half screen displays Review transactions screen Point history report Keyholder history report Transaction history report all sort options Ar...

Страница 42: ...em default values with most screen fields requiring a numeric range entry For example the default range for keyholders is 1 999999999 to reduce waiting time while a report is generating enter the smal...

Страница 43: ...strprt screen follows Point History Sample Report 06 27 96 Packlett Industries PAGE 1 14 36 Point History KeyhldID Keyholder Name Date Time Access Description ________ _______________ _____ ____ _____...

Страница 44: ...N 0120 ELEVATOR FREIGHT CAR 06 26 96 15 40 31 MANUAL LOCK TRANSACTION HISTORY REPORT The transaction history report excprprt lists all transactions according to selected criteria The transaction repor...

Страница 45: ...en follows 11 15 96 SHARPSMITH LABS INC Page 1 10 34 Access Control Transaction Report Point Point Description Zone Date Time Access Type Keyholder Keyholder Name Key No _____ _______________________...

Страница 46: ...ntic Racing PAGE 1 15 01 Alarm Master List Alarm No Alrmtime Alrmdate Point Zone Resp Time Resp Date Clear Time Clear Date Serviced By ________ ________ ________ _____ ____ _________ _________ _______...

Страница 47: ...__ 1055699 83383 MAITLING JACK 0 1 1 1061128 84128 LYONS CINDY 0 1 1 1086201 83361 DENEUVE DENISE 0 0 1 1099004 86660 SMITH PAULA 0 1 2 1100015 87083 MACKLING JACKIE 0 1 1 1116345 88883 FLYNN SEAN 0 1...

Страница 48: ...the requested download ERR Receiving Data Information successfully transmitted by the host but the target device was unable to receive 06 27 96 Nevadia Industries PAGE 1 15 03 Download Status Report S...

Страница 49: ..._ _________________ _______ _______ ____ 10556 MAITLING JAMES 0 3120 808SX RDR 2 04 02 96 16 48 12 0 10564 LYONS SHELLEY 0 3120 808SX RDR 2 04 02 96 16 48 12 0 10569 MCDUFF GORDON 0 3120 808SX RDR 2 0...

Страница 50: ...OLLER 222 POLLER STOPPED 2 4 808 422 POLLER 224 POLLER STARTED 12 REALTIME PASSBACK ZONE REPORT Therealtimepassbackzonereport rpasrprt isessentiallythesamereportasthepassbackzone report described earl...

Страница 51: ...ack Detail Report Keyholder Key No Keyholder Name Tenant Pzone Vzone _________ ________ _________________________ ______ _____ _____ 223141 188954 McDaniels Jeff 0 1 1 237473 140226 Wellington Lambert...

Страница 52: ...terfileentryproceduresareusedmorefrequentlythanothers Forexample keyholder data is usually added changed and deleted daily On the other hand additions or changes to system configuration information ma...

Страница 53: ...e The first screen key_entr is accessed from Keyholders first item in the fmntmenu menu the other screens are displayed using F2 after the previous screen has been saved IMPORTANT 1 All keyholder data...

Страница 54: ...e DO34 Default is No facility code Key Number Conditional Enter an eight digit maximum key number If you do not wish to select a key number at this point the system default 0 is entered automatically...

Страница 55: ...building Trace monitors doors readers and records Using Trace causes an extra key trace log message This feature is sometimes desirable if the keyholder is a visitor see previous field Default is N Pr...

Страница 56: ...gned with the following two exceptions 1 Do not assign a keyholder more than one access code for a single NexSentry 8xx series or 422 ACU 2 The system will not allow you to combine two access codes wi...

Страница 57: ...re not logged Access Group Optional Enter an access group number no limit that applies to this keyholder the system automatically enters the access group description Default is 0 No access group Note...

Страница 58: ...the key_copy screen is an important timesaving feature A sample screen follows From Enter an existing keyholder ID zoom available The system automatically supplies the key number and the keyholder nam...

Страница 59: ...ata entry is the same as for the keyholder access entry screen empgentr The keyholder access allows only assignment permissions without access to keyholder screen A sample screen showing egrpentr and...

Страница 60: ...ented to a reader the ACU makes the access decision In some circumstances the host computer may override an access request denied by an ACU Smart Failsoft These codes work only if the ACU is in smart...

Страница 61: ...RECEIVING When screen entry is completed press F6 to store the data the access code definition screen acodentr displays automatically ACCESS CODE DEFINITION acodentr ThisscreenisusedtoenterthereaderI...

Страница 62: ...odentr press F2 to display the elevator definition screen eleventr example below 2 Enter the output contact IDs usually wired to the elevator cab floor buttons to be closed activated when access is gr...

Страница 63: ...ntrolled and downloaded access codes may be combined in the same access group but see Warning at the end of this subsection ACCESS GROUP DEFINITION agrpentr Access Code Required zoom available Enter a...

Страница 64: ...only one downloaded access code per ACU ACCESS OVERRIDE ENTRY Accessoverridecodesaretypicallyusedforvisitorstorestrictorallowaccesstospecificlocations for specific time periods This is a host functio...

Страница 65: ...display Keyholder ID Required zoom available Enter the applicable keyholder ID keyholder name automatically displays Allowed Optional Enter Y or N as appropriate for the individual keyholder Default i...

Страница 66: ...ding Date and Time Enter the project s ending date and time in the formats MM DD YY and HH MM Store F6 data when completed the project definition prd_entr screen automatically displays Enter the appli...

Страница 67: ...ime code Start Required Enter a start time using 24 hour notation with an intervening colon Examples 08 45 8 45 a m 19 15 7 15 p m If the start time is entered incorrectly the systemeitherpreventsfurt...

Страница 68: ...has access to the entire system at all times The systems owner may also be the system administrator The default tenant code is 0 zero usually the system owner who has access to the entire system at al...

Страница 69: ...Definition Areas SE 422 PIN Definition Pollers SE 422 Hardware Definition Devices Dialer Entry Readers Site Entry Definition Points ABA Configuration Entry Auto Opens Activates DKR Configuration Entry...

Страница 70: ...areas Reporting keyholder zone report may be by zone or area with the area report listing the zones contained in each area Assign a number and optional description for the area using areaentr enter t...

Страница 71: ...r 10 Elevator Elevator control poller Internal No physical connection 11 Database Database poller Internal No physical connection 12 Burle Burle closed circuit television CCTV 13 Vicon Vicon camera sw...

Страница 72: ...Opto 22 input output controllers CCTV switchers Radionics alarm panels One or more additional SE 6000 systems used as local controllers With the exception of the NexSentry 8xx series and 422 ACUs eac...

Страница 73: ...when setting up any device A sample screen follows Device ID Required Enter a unique four digit maximum device ID number in the range 1 9999 Device Description Optional Enter a 20 character maximum d...

Страница 74: ...RDI 1 32 9 RLC 1 8 10 808SX SN 1 16 11 818SX SN 1 16 12 AMDI 102 103 1 16 13 NexSentry 1 16 14 Camera 1 only 15 SE422 1 16 16 Radionics 1 only 17 Polaroid ID 4000 1 16 18 818SC 1 16 19 808SXT 1 16 21...

Страница 75: ...AthroughF nameandpassword The security codes A through F control the degree to which the operator may add change delete the system parameters from the ACU terminal port Code A has the most privileges...

Страница 76: ...4 1060 5 1050 1060 Digital Keys 5 Aux Type Conditional Auxiliary key type A second key type other than the one entered in the previous field can be entered here if applicable Default is 0 0 None 1 10...

Страница 77: ...e information and press F6 Store to complete the NexSentry device configuration A sample nexsentr screen follows Level Name Password Required Thesefirstthreefieldsareenteredtoidentifyuptoeight operato...

Страница 78: ...nal Enter the operator override report number if a report has been created see applicable ACU manual The report states the actions that will be taken by the ACU if for example a manual unlock or a shu...

Страница 79: ...icating if the PIN should be displayed once calculated Default is Y PIN Timeout Optional Enter the maximum number of seconds allowed between key presentation and PIN entry Default is 10 Max PIN Retrie...

Страница 80: ...le ACU manual NOTE The Level Name and Password fields are specific to individual SE 422s and apply only to operatorsloggingindirectlyviatheACU sterminalport ThefieldsarenotpartoftheSE6000 control para...

Страница 81: ...efault PIN seed value entered on the pndfentr screen see Entering Default PIN Digits and Seed for an SE 422 in this section Default is 0 PIN Digits The number of digits in the PIN code for this SE 422...

Страница 82: ...l feature Tracks number of meals taken by a keyholder 4 Guard Tour optional feature Monitors guard check in activities during guard rounds 5 Elevator Control Controls and limits keyholder access to fl...

Страница 83: ...when the ID is entered Sensor Required Enter the sensor port number of the ACU to which this reader is connected Enable Point ID Conditional zoom available Indicates a point ID that must be activated...

Страница 84: ...ot apply T A Dir Time and attendance direction If the time and attendance feature is used enter N None I Global In or O Global Out The default is N 0 Unlock Time Optional for NexSentry 8xx series and...

Страница 85: ...onfiguration Menu confmenu screen appears 3 Select Readers and the Reader Entry rdr_entr screen appears 4 Select F5 Add Mode 5 Enter all necessary information making sure that you enter 8 in the Reade...

Страница 86: ...ltiple Occupancy zone requires that the last two keyholders present their keys at the same time first one and then within the prescribed time period the other unlocking the door READER REPORT DEFINITI...

Страница 87: ...Enter the proximity type 0 Sensor interface 1 DigiKey reader Proximity Code Enter the proximity reader node number 0 None 15 1st proximity reader node number 16 2nd proximity reader node number Keypad...

Страница 88: ...ation Door Output Relay Enter the number of the 422 relay DKR Configuration Enter the ID number Valid ranges of numbers is from 1 9999 ABA Configuration Enter the ID number Valid range of numbers is f...

Страница 89: ...etailed information DKR Configuration Enter the ID number Valid range is from 1 9999 VIPEnable Optional AY N Ofieldtoenable disabletheVIP OindicatesVIPonly Default is N VIP Active During Building Mode...

Страница 90: ...n the system Note There are eight hardware types exclusively input and or output contacts that require a type number and a point number when being set up in the database You establish these devices us...

Страница 91: ...ay be connected directly to other device types For an ACU the number entered is the number of the sensor connection to the device For devices with directly connected points e g Optomuxboards alarmmoni...

Страница 92: ...s Note that this is used with alarm generated points If it is a door switch or a REX it is defined on the second page of the Reader screen The word report in this context identifies a previously defin...

Страница 93: ...nts through reporting when using an intelligent ACU Mod Optional Log messages and system action can be modified using the custom transaction modifier codes A B etc see Section 6 System Administration...

Страница 94: ...reports are assigned using screens described in the device entry subsection For complete descriptions on how to use the report definition screen for the various ACU types please refer to the respectiv...

Страница 95: ...etic stripe card readers and keypads allowing PIN entry The subdevices as connected to the SE 422 are known as nodes on the SE 422 communications network A node is further defined by assigning it a po...

Страница 96: ...for the off site ACUs A sample screen follows Device ID Required zoom available Enter a four digit device ID number system automatically displays device description Associated Poller ID Required zoom...

Страница 97: ...for example every two minutes Minimum Call Minimum elapsed time before dialing remote site for log messages in hours for example every six hours MaxCall Maximumelapsedtimebeforedialingremotesiteforlo...

Страница 98: ...nge 1230 through 1239 would be matched ABA CONFIGURATION ENTRY The ABA American Banking Association configuration entry screen is used to define codes to be read from a standard ABA magnetic stripe ca...

Страница 99: ...take that are based on the expiration date Use Site Code as Key Y N Use the site code as the key number DKR CONFIGURATION ENTRY The DKR Digital Key Reader configuration entry screen is used to change...

Страница 100: ...id range for on time off time and duration is 0 65535 clock ticks The default is 0 uses factory set predefined behavior USER DEFINED INFORMATION Certain field titles on the keyholder record screens ca...

Страница 101: ...an also use this feature on an SE 6100 or below from your console This requirement is due to the SCO Unix graphic memory limitation The function has several built in HELP maps and drawing instructions...

Страница 102: ...labels large and small Outpt Pt Output point icon Rectangle with a smaller rectangle crossing it point 4103 on sample map Camera Pt Camera point icon Rectangle with a small projection to the left poi...

Страница 103: ...1 62 63 RO4 4 state 9 64 10 65 Input points are always on 11 66 sensor 1 contact 1 75 12 67 VIP 2 state 13 68 14 69 SI 4 state 15 70 71 16 72 73 MSR 2 state 17 74 18 75 SE 422 Output Table 0 1 2 3 4 5...

Страница 104: ...ic range entry For example the default range for keyholders is 1 999999999 to reduce waiting time while a report is generating enter the smallest range of numbers for each category which will still pr...

Страница 105: ...le user defined field C and floor The master report includes all the keyholder information entered on page 1 of the keyholder entry screen plus address phone number and user defined field 7 Also the m...

Страница 106: ...RITY MGR 18 247666 176 KERR KATIE 11 0 0 248112 765 LOWE LORRAINE 11 7 234 5678 SECURITY RECEPTIONIST 2 249343 453 GREENWOOD LORI 11 7 901 2345 SECURITY RECEPTIONIST 1 08 02 96 McArthur Complex PAGE 1...

Страница 107: ...epartment location job category shift status remarks phone trace visitor and badge issue information A sample screen follows KEYHOLDER ACCESS ASSIGNMENT REGULAR SAMPLE REPORT 06 06 96 BARON PARK HOLDI...

Страница 108: ...o987 65 4321 Addr2 Apt 12B Location 1 Tulip Grove Main Tenant 1 Addr3 Tulip Grove CA 91999 Job Cat 6 Software Engr P I N 2198 Privledge YES Shift 0 N A Remarks Status 0 N A Phone 224 8089 Trace NO Vis...

Страница 109: ...le group or a range of groups as required A sample screen follows 05 02 96 Soames Industries Page 1 11 26 Access Code Master List Code Code Description Reader Reader Description Tmcd Start End Mon Tue...

Страница 110: ...ent fail soft report function used in the event of a communications failure lists keyholder access permissions for each 708P in the system The report begins a new page for each device and shows the re...

Страница 111: ...FI GI Y Y Y Y Y Y Y Y 61096 GUARD NEW Y Y Y Y Y Y Y Y 61099 1030 ALT D P Y Y Y Y Y Y Y Y PROJECT REPORT The Project Report includes number description start stop times and dates and current status NOT...

Страница 112: ...Inactive KEYHOLDER PROJECT REPORT The Keyholder Project Report includes keyholder ID name project ID and description and current status A sample keyholder project report screen follows NOTE This repor...

Страница 113: ...rides actual and reported project status may differ A sample reader project report screen follows READER PROJECT REPORT SAMPLE REPORT TIME CODES This report lists all time codes set up in the database...

Страница 114: ...N 3 WEEKENDS HOLIDAYS 00 00 23 59 N N N N N Y Y Y HOLIDAYS This report lists all holidays that have been entered into the system A sample screen follows HOLIDAY CODES SAMPLE REPORT 03 25 96 Jamestown...

Страница 115: ...company department location and job category information The report screens are identical for all four a sample follows COMPANY DEPT LOCATION JOB CAT SAMPLE COMPANY REPORT 03 25 96 Security Electronic...

Страница 116: ...TE SITE FIRE ALARM CALL 777 1212 AND NOTIFY LOCAL FIRE DEPT NOTIFY OPERATIONS MANAGER PAGER 12345 LOG EVENT IN SHIFT LOG BOOK MAPS The map report lists all points incorporated into user defined system...

Страница 117: ...llers in the system A sample screen follows POLLERS SAMPLE REPORT 03 25 96 Global Software Page 1 08 49 Poller Master Report Poller Date In Comp Poll Prim Poller Type Desc Disabled Zone Zone Desc ____...

Страница 118: ...p Poll Address Prim Device Type Desc Disabled Zone Zone Description ___________________________________________________________________________________________________ 1 HOST 0 0 0 1 Host NO 0 OUTSIDE...

Страница 119: ...Y Y Y Y Y Y Y 296 RM A WEST ENTRY 1 16 1 2 Acc Ctrl 1 N A 2245 2244 Tmcd Start End Mon Tue Wed Thu Fri Sat Sun Hol ____ _____ _____ ___ ___ ___ ___ ___ ___ ___ ___ 1 00 00 23 59 Y Y Y Y Y Y Y Y 07 16...

Страница 120: ...Latch Close Output Bldg Open Y N Y Bldg Limited Y N Y Bldg Closed Y N Y Time Code 1 1 Time Code Time Code Contact Number Print Asterisk With Log N Prevent Building Closure N 03 25 96 Security Electron...

Страница 121: ...Code C TIM JONES TJO123 Alt Facil Code A000 DIALERS The two dialer report types detail the remote dialup interface RDI devices defined for the system or those RDI devices which have experienced commu...

Страница 122: ...ned for the system and gives the configuration parameters A sample screen follows ABA CONFIGURATION SAMPLE REPORT 03 25 96 Security Electronics Page 1 09 17 ABA Configuration Report Configuration ID 1...

Страница 123: ...SE 422 PIN MASTER REPORT This report lists keyholders having system calculated SE 422 PIN numbers A sample screen follows 06 12 96 Lotus Refineries Page 1 15 21 DKR Configuration Report Beeper Times...

Страница 124: ...22 SE 422 Quick List Keyholder Key No Keyholder Name Dept Jobcat Phone Title Loca Floor 422Pin ___________ ______ _______________________ ____ ______ ___________ __________ ____________ ______ 6109 18...

Страница 125: ...menu Depending on the operator s program security level some or all of these functions may not be available A sample screen follows SECTION ORGANIZATION The procedures in this section are in the orde...

Страница 126: ...g on and password must be used to access this screen If you are already logged on with your regular password first log off in the normal way then log on again using the administration log on and passw...

Страница 127: ...all transactions Monitoring Security Level System code 0 1 or 2 indicating the user s monitoring data changing capabilities Monitoring security level 0 allows full monitoring changing capabili ties i...

Страница 128: ...omplete functionality 2 View maps only no control capabilities MODIFY PASSWORDS mod_pass Usethemodifypasswordscreentochangeanexistingpassword mustbeloggedinas addusers Enter the user name then follow...

Страница 129: ...mber four digits maximum Enter a description 30 characters maximum Press F6 Store then press F2 for the program security level definition screen PROGRAM SECURITY ENTRY DEFINITION pg1_entr Press F7 the...

Страница 130: ...ting program security using the foregoing methods 2 To delete an item first select as shown above then use Esc d r COPY SECURITY mnaccopy It may be easier to copy an existing security level and make c...

Страница 131: ...96 Eton Engineering Page 1 13 02 Login Name Tenant Security Keyholder _________________ ______ _________ _________ anderson 0 1 1123456 melville 0 1 1334229 smith 0 1 1348876 DISPLAY CURRENT DATE AND...

Страница 132: ...SYSTEM CONFIGURATION syclmenu CONTROL FILE MAINTENANCE ctrlentr For informational custom reporting purposes certain field titles that display in keyholder record screens key_entr and key1entr can be c...

Страница 133: ...edbyatimecode automatically perform the task entered in the activate field at the start of the code and the task entered under the deactivate code at the end of the time code A sample screen follows E...

Страница 134: ...ced by this event applies to a specific time code enter the time code number Perform Task ID Required Enter the task ID number TASKS taskentr Used to set up tasks for the task event subsystem Tasks mu...

Страница 135: ...time in the Unlock Time field of the reader entry screen 56 BUILDING OPEN Set building mode to OPEN 57 BUILDING LIMITED Set building mode to LIMITED 58 BUILDING CLOSED Set building mode to CLOSED 70 D...

Страница 136: ...__ __________ 42 UNLOCK DOOR 708 2 ENTER ZONE B Man Open N EVENTS 7120 708 2 ENTER ZONE B 62 0 KEY NOT ACTIVE No Activity Tmcd Start End Mon Tue Wed Thu Fri Sat Sun Hol ____ _____ _____ ___ ___ ___ __...

Страница 137: ...nt via the event task subsystem Enter 1 to activate the task enter 2 to deactivate the task Time to Acknowledge Enter a value in minutes to allow for alarm acknowledgment If the alarm is not acknowled...

Страница 138: ...tem keeps a small area of disk space available to store the last 20 events for all individual keyholders in the system The keyholder history file is listed using the keyholder history report Point Log...

Страница 139: ...and written to the download file If the download transfers are unsuccessful the number of records created can increase the download file size to a point where systemperformanceisaffected andthesereco...

Страница 140: ...ivesalljournalinformationexceptforthecurrentday Archivingisperformed using the jourarch screen JOURNAL REPORTING jourrprt This function reports all changes to the database The report prints the column...

Страница 141: ...Security Maintenance function controls access to the information shared by the SE 6000 and the Polaroid ID 4000 Identification System It also controls access to selected fields in the keyholder record...

Страница 142: ...ing all users entered into the ID security feature along with tenant and group definition information A sample of a partial screen and report follow 06 26 96 Campbell Engineering 07 26 ID Security Mai...

Страница 143: ...performance when inefficient communication facilities are used 3 On 708P ACUs the host port speed on the device is set with dipswitches Both the device and the poller must be set for the same speed 70...

Страница 144: ...l devices controlled by the poller KEY INVENTORY invtmenu This feature is used to control system keys This is an optional feature and does not effect operation The menu screen is accessed from the mai...

Страница 145: ...______ 1 AVAILABLE 2 ASSIGNED 3 LOST 4 UNUSABLE 5 DAMAGED 6 TERMINATED 7 REISSUED 8 RECOVERED 9 PREVIOUS OWNER 10 RESERVED KEY INVENTORY ENTRY cdinentr This function is used to add change key inventor...

Страница 146: ...RDINS ROBERT 33249 06 23 96 13 25 ASSIGNED 36427 JERRY TIMOTHY 36426 06 23 96 13 44 ASSIGNED 37441 JUDD AL 37444 06 23 96 13 51 ASSIGNED PARKING STICKERS stkrmenu Thisfeatureisusedtocontrolparkingstic...

Страница 147: ...reen and report follow 06 25 96 Security Electronics Page 1 16 00 Parking Sticker Report Keyholder Keyholder Name Sticker License _________ _______________________________ _______ _______ 28870 TERRY...

Страница 148: ...lock ctrlprnt ctrlinp ctrldoor selzone ctrlout ctrldev devstat viewmap insrtns response download psbkfrgv manacc devcomm ctrlmenu dispmap othrmenu mainmenu alrmserv revtran monitor Full Screen rem_dev...

Страница 149: ...A 2 APPENDIX A SYSTEM SCREEN TREES acrtrprt almarprt whowhere excprprt phstrprt chstrprt accsmenu mainmenu ky2nrprt evptrprt rpasrprt downrprt Screen Location Tree Security Management Reports...

Страница 150: ...eleventr agrpentr instentr usrdmenu compentr loc_entr usraentr usrbentr job_entr deptentr d818entr autoentr pnt_entr rdefentr siteentr nodeentr pndfentr rdr2entr areaentr1 areaentr mainmenu egrpentr d...

Страница 151: ...rt zonerprt dev_rprt rdr_rprt pnt_rprt autorprt mainmenu accrmenu siterprt dconrprt rdefrprt con_menu egrprprt emrdrprt aassmenu p422rprt tentrprt loc_rprt comprprt tmcdrprt acodrprt fs_rprt agrprprt...

Страница 152: ...EM SCREEN TREES A 5 Screen Location Tree Key Inventory invtmenu statentr cdinrpt statmenu statrprt cdientr mainmenu stkrentr stkrprt stkrprt1 stk1entr stkrrprt stkrmenu mainmenu Screen Location Tree P...

Страница 153: ...accopy pgacentr evenentr tranentr db_menu showuser mod_pass addusers mainmenu sys_menu josprprt jourrprt alrmcln accsarch jourarch bkup downcln dbstats ctrlentr taskentr pg1_entr showdate Screen Locat...

Страница 154: ...ack status for a single keyholder or for all keyholders in the system manacc Allow entry for keyholder who does not have a key operator and keyholder data logged download Extract database information...

Страница 155: ...nter modify information specific to NexSentry d808entr Enter modify information specific to 808S d818entr Enter modify information specific to 818x d422entr Enter modify information specific to SE 422...

Страница 156: ...rmation loc_rprt Report all user defined field C information job_rprt Report all user defined field D information instrprt Report all alarm instructions map_rprt Report all map names for specific poin...

Страница 157: ...t Cancel submitted reports beepentr Define terminals for alarm response beep regardless of system area where operating syclmenu Menu to system configuration functions ctrlentr Change report titles use...

Страница 158: ...host memory 12 Invalid Facility Code Access denied wrong facility code 1030 1040 keys only 13 Manual Unlock Reader door manually unlocked 14 Manual Lock Reader door manually locked 15 Auto Unlock Rea...

Страница 159: ...t functioning properly 41 Poller Params Reloaded Host has initialized a poller 42 Still Held Open DOOR HELD OPEN Second alert message 43 Input Point Active A GENERAL input has been activated 44 Input...

Страница 160: ...o remote dial up device encountered 67 Output Activated Output contact manually or automatically activated 68 Output Deactivated Output contact manually or automatically deactivated 69 Invalid PIN Ent...

Страница 161: ...cations 97 Parameter Load Error Host poller initialization failed 98 Tran File Almost Full Archive history file approaching capacity Archive immediately 99 Database Error Data to database failed There...

Страница 162: ...hould be Closed 8xx series ACU in time period where it should be closed 128 Can t Close Bldg Key 8xx series ACU cannot be placed in closed mode because proper key not presented 129 Can t Close Bldg Us...

Страница 163: ...et from devices menu 155 Request Reset Keys Operator initiated key reset from devices menu 156 Reset Device Okay Affirmative response following device reset command 157 Reset Key Okay Key information...

Страница 164: ...Zone Restoral 206 Line Card Restored 207 General Opening Report 208 Zone Opening Report 209 General Closing Report 210 Zone Closed 211 General Cancel Report 212 Zone Cancel Report 213 Radionics Unit P...

Страница 165: ...ut Problem RDI unable to communicate with 808S 304 RDI Hardware Problem RDI has detected an error with its operating hardware 305 RDI Modem Problem RDI has detected a modem error 306 RDI Alarm Table E...

Страница 166: ...ferred Key 147 Device Cannot Connect 131 Device Online 54 Device Reset 30 Disk Almost Full 242 Door Closed Forced 19 Door Closed Held 20 Door Forced Open 17 Door Held Open 18 Door Report Shunted 112 D...

Страница 167: ...RDI Host Comm Error 308 RDI Is Full 300 RDI Is Too Cold 302 RDI Is Too Hot 301 RDI Modem Problem 305 RDI Timeout Problem 303 Redundancy Off 71 Redundancy On 70 Remote Comm Ended 85 Remote Trans Recei...

Страница 168: ...ay Data Base Stats N N N dconrprt 808 Device Configuration N N N deptentr Dept Y Y Y deptrprt Dept N N N dev_entr Devices Y Y Y dev_rprt Devices N N N dialentr Dialer Entry Y Y Y dialrprt Dialers N N...

Страница 169: ...r Rpt N N N stkrrprt Parking Sticker Display N N N summdel Delete Ticket Records N N N syclmenu System Configuration N N N sys_menu System Administration N N N taarch Transaction Archiving N N N tacfe...

Страница 170: ...Projects 5 10 Access Group 1 2 Access Group Entry 4 11 Access Override Entry 4 13 Activate Deactivate Codes 6 11 ACUs 1 3 Add Users addusers 6 2 Adding Changing Data 1 14 Adjustable Baud Rate 708P 800...

Страница 171: ...ntrol File Maintenance ctrlentr 6 8 Control Function Keys Control Doors Function Keys 2 6 Control Input Function Keys 2 5 Control Locks Function Keys 2 4 Control Output Function Keys 2 5 Control Zone...

Страница 172: ...ing the Database 1 8 Poller Initializatin 1 8 Definitions File Maintenance 1 7 Definitions General 1 2 Access Code 1 2 Access Group 1 2 Alarm Contract 1 2 Company 1 2 Department 1 2 Device 1 2 Event 1...

Страница 173: ...i Passback Control 1 6 Definitions System Software 1 5 Installation Flexibility 1 5 Integrated Software 1 5 Open System Design 1 5 Portability 1 5 Response Time 1 6 Definitions Tenant 1 3 Deleting a C...

Страница 174: ...us Before Transmission 3 7 Error in Receiving Data 3 7 Error in Transmitting Data 3 7 Received and Processed 3 7 Transmitted 3 7 Unprocessed 3 7 Download Status Report 3 6 Sample Report 3 7 E Elevator...

Страница 175: ...R Configuration 4 48 NexSentry 4 26 Points 4 39 Pollers 4 19 Readers 4 31 Site Entry Definition 4 46 Zones 4 18 Heat Sensors 1 4 Holidays 4 16 5 11 I ID Security Group Entry ID2_ entr 6 18 ID Security...

Страница 176: ...eports 5 2 Project Assignment 4 6 Keyholder History 1 7 Keyholder History Report 3 2 Sample Report 3 3 Keyholder ID 1 3 Keyholder Loading loadmenu 6 17 Keyholder Zone Report 3 8 Sample Report 3 8 Keyh...

Страница 177: ...ems 1 18 Elevator Control 1 18 Guard Tour 1 18 ID 4000 1 18 IQ 1 17 Parking Control 1 18 Remote RDI 1 18 Time and Attendence 1 18 Visitor Control 1 18 Other Functions 2 9 Printer Control 2 9 Output Po...

Страница 178: ...s Code Master List 5 6 Access Group Master List 5 7 Access Override 5 7 Auto Open Activate 5 17 Company Dept 5 12 Devices 5 15 Dialers 5 18 DKR Configuration 5 20 Holiday Codes 5 11 Intelligent Fail S...

Страница 179: ...Screen Function Timeout 2 13 Storing Data 1 14 System Administration Add Users 6 2 Database Maintenance 6 14 Display All Users Logged In 6 7 Display All Valid Logins 6 7 Display Current Date and Time...

Страница 180: ...Transactions 1 3 Transactions tranentr 6 12 Two Man Rule 1 6 U User Defined Information 4 49 Using Screens and Fields 1 12 Moving Between Data Fields 1 12 Moving to Prior Screens 1 13 Selecting Scree...

Отзывы: