background image

TYPE  COQ  RELAY 

CONTACTOA  SWI 

/-TEST 

SJI'ITCH 

- OVERCURRE!ff  ELEMENT 

3 Hl.wDIM>'S 

TEST JACK 

BAS£  7£RM9, 

FRo.-vr 

CHA.S�JS  OPERATED 

26-D-1428 

ShORT!'-"' 

SW/TCH 

Fig.  1-Internal Schematic Of The COQ Relay In 

FT 

Case. 

coil  connected  in  the  trip  circuit. 

When  the 

coil  is  energized  a  spring-restrained  armature 
releases  the  white  target  which  falls  by 

gravity  to  indicate  completion  of  the  trip 

circuit. 

The  indicator  may  be  reset  from  out­

side  of  the  case. 

Negative  Sequence  Current  Filter 

The  negative  sequence  current  filter  con­

sists  of  a  reactor  and  an  adjustable  resistor. 

These  elements  are  connected  in  such  a  manner 

that  the  output  of  the  filter  is  proportional 
to  the  negative 

sequence  input. 

CHARACTERISTICS 

The  COQ  negative  sequence  relay  is  available 

with  the  following  negative  sequence  current 
taps: 

3-25 

3-5 

4.2 

4.6 

5.0 

These  tap  values 

represent 

the  current 

transformer  secondary  amperes  which  corres­
pond  to  one  per  unit  generator  current. 

At 

these  values  of  negative  sequence  currents, 
the  moving  contact  will  leave  the  time  dial 
stop  and  reach  the  stationary  contacts  in  a 
time  as  determined  by  the  time  dial  setting 

and  as  shown  by  Fig. 

3· 

For  example,  with 

time  dial  setting  of 

"4" 

the  relay  will  close 

its  contacts  in 

30 

seconds  with  the  above  tap 

currents  applied  to  the  relay. 

As  shown  by  the  curves  of  figure 

2, 

the 

relay's  characteristic  is  defined  by  a  genera-

tor  characteristic 

I�T 

K. 

The  relay  charac­

teristic  is  such  that  it  coincides  with  the 
generator  characteristic  at  l  per  unit  nega­
tive  sequence  current  but  at  higher  values  of 
negative  sequence  current, 

the  relay  charac­

teristic  is  substantially  parallel  and  slight­
ly  less  than  the  generator  characteristic. 

In 

this  manner, 

a  suitable  margin  of  safety  is 

obtained  between  the  two  characteristics. 

Figure 

defines  the  relay  characteristics 

for  two  generators  - one  with  a 

permissible 

constant  of 

"3

0 "   and  the  other  with  a  constant 

of 

"90". 

The  time  dial  settings  for  these 

constants  are 

"4" 

and 

"11" 

Similar  protection  for 

other 

I

T  constants  between 

"30" 

respectively. 

generators  with 

and 

"90" 

is  ob-

tained  by  settings  of  the  time  dial.  Figure 

shows 

the  necessary  ti�e 

dial  settings  for 

various 

I�T 

constants. 

By  referring  to  this 

figure,  the  time  dial  can 

be 

set  so  that  the 

relay  protects 

different  generators  whose 

l�T 

constants  range  from 

"30" 

to 

"90". 

Typical  operating  characteristics 

relay  are  shown  in  flgure 

4. 

of  the 

Minimum  pickup  of 

t�e  relay  is  approximately 

.G  per 

u�it. 

The 

burdens 

and  thermal  ratings  are  listed 

under  Energy  Requirements. 

3-25 

Circuit 

The  main 

contacts  will 

safely 

close 

30 

amperes  at 

250 

V. 

d-e,  and  the  switch  contacts 

will  safely  carry  this  current  long  enough 

to 

trip 

breaker. 

As  shipped  from  the  factory, 

the  operation 

indicator  and  the  contactor  switch  are  con-

nected  in  parallel. 

This  circuit  is  suitable 

for  all  trip  currents  above 

2"25 

amperes  d-e. 

I f   the  trip  current  is  less  than 

2.25 

amperes, 

there  is  no  need  for  the  contactor  s witch  and 
it  should  be  dlsconnected. 

To  disconnect  the 

coil  remove  the  short  lead  to  the  coil  on  the 

front  stationary  contact  of  the  co�tactor 

switcho 

This  lead  should  be 

fastened 

www 

. ElectricalPartManuals 

. com 

Содержание COQ Series

Страница 1: ...end and a pin and olive bearing on the upper end Both shaft bearings as well SUPERSEDES I L 41 277A 4 enotes changed from superseded issue as their 2djustable pins are removable A set screw and nylon plug locks the bottom pin in position and a sho lder nut of the time dial locks the top pin in position Attached to an insulated section of the disc shaft is a rigid arm holding a small silver hemisph...

Страница 2: ... generator characteristic at l per unit nega tive sequence current but at higher values of negative sequence current the relay charac teristic is substantially parallel and slight ly less than the generator characteristic In this manner a suitable margin of safety is obtained between the two characteristics Figure 2 defines the relay characteristics for two generators one with a permissible consta...

Страница 3: ...RACTERISTICS TIME DIAL 3 f SET J II 2 5 2 1 5 1 r i GENERATORS CHARACTERISTIC 12 2T 30 2 12 T 30 _ 1 t I 1 s 6 7 8 9 1 0 1 5 2 2 5 3 4 5 6 7 8 9 10 NEGATIVE SEQUENCE CURRENT IN PER UNIT 1 0 PER UNIT TAP VALUE CURRENT Fiq 2 Comparison 0 Relay Characteristic With Generator Characteristic 27 D 554 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 4: ...w w 1 z u w J cr 50 _j I u I I I v I 0 rr i 0 I cr 40 w z J w I l l lJ J I I 30 z I I I J I I 0 lL 0 w n 0 20 J 0 u f _j 0 1 0 10 z 0 w f 2 3 4 5 6 7 8 9 10 II TIME DIAL SETTING 27 D 5609 Fig 3 Tirne Dial Setting Versus Permissible Constant Of Generator 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 5: ...5 20 15 10 9 8 7 6 5 4 3 2 5 2 1 5 TIME DIAL SETTING 6 _ 1 l 1 l t I 5 6 7 8 9 1 0 1 5 2 2 5 3 4 5 6 7 8 9 10 NEGATIVE SEQUENCE CURRENT IN PER UNIT 1 0 PER UNIT TAP VALUE CURRENT Fig 4 Typical Operating Curves Of The COO Relay 27 D 5544 5 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 6: ...o be protected The time dial indicates a I T K curve of a generator for which the relay protects By turning the time dial the relay can be used to protect generators with I T constants varying from 30 to 90 as shown in Fig 3 ADJUSTMENTS AND MAINTENANCE All the relays should be inspected peri odically and the time of operation should be checked at least once every six months or at such other time i...

Страница 7: ...f the test connections is shown in Fig 6 Next adjust the spring tension until the relay will close contacts in 90 seconds with 5 2 ampe re s single per unit negative between terminals 8 phase tap value or one sequence current applied and 14 This adjustment is made by means of the spiral spring ad juster All spring convolutions must be free TRIP CIRCUIT Universal Trip This combination uses a 2 0 am...

Страница 8: ... RESPONSE TO ZERO SEQUENCE 27 D 5445 Fig 5 Diagram Of Test Connections Of The Type COO Relay For Adjusting Filter To Have No Response To Zero Sequence 8 ordering parts always give the complete name plate data ENERGY REQUIREMENTS The burdens of the type COQ Relay are as follows Watts Volt Amps Power Factor at 5 Amps at 5 Amps Angle 5 3 5 3 00 0 0 98 90 Lag 4 0 7 25 56 Lag TIMER STOPS 10 s i ER 3v o...

Страница 9: ... 0 92 TlltM tCKif w l U leQ 32 STVD FOR PI HEL LOCATION TM CK PANI L MTG FOR PRo JECTION ____ T fPE MTC 1 Olti J KR INT RNALSCH CUT OUT r Q SEHI FLUSH MOUNTING 0 rt2l j M TIC f Otl JEt r c GON_ T _ c rit c JTOUTl OR P1 0J CT ON MTC T IN PI NEI I PANEL I OCA1 0trrl FOR SEMI FW ot TVPE I m Fig 9 0utline And Drilling Plan Of The MlO Projection Or Semi Flush FT Flexitest Case 16 B 2477 9 w w w E l e c...

Страница 10: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 11: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 12: ...WESTINGHOUSE ELECTRIC CORPORATION METER DIVISION NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Отзывы: