background image

TYPE  COQ  RELAY 

(dead-ended) 

under  the  small  filister  head 

screw  located  in  the  Micarta 

base  of  the 

contactor  switch. 

CONTACT  CIRCUIT  CONSTANTS 

Universal  Trip  Circuit 

Resistance  of  0.2  ampere  Target  ....  2.88  ohms 

Resistance  of  2.0  ampere 

Contactor  Switch .................  0.25  ohms 

Resistance  of  Target  and 

Switch  in  Parallel ...............  0.23  ohms 

INSTALLATION 

The  relays  should  be  mounted  on  switch­

board  panels  or  their  equivalent  in  a  location 
free  from  dirt,  moisture, 

excessive  vibration 

and  heat.  Mount  the  relay  vertically  by  means 

of  the  two  mounting  studs  for  the  type  FT  pro­
jection  case  or  by  means  of  the  four  mounting 
holes  on  the  flange  for  the  semi-flush  type  FT 
case. 

Either  of  the  studs  or  the  mounting 

screws  may  be  utilized  for  grounding  the 
relay. 

The  electrical  connections  may  be  made 

direct  to  the  terminals  by  means  of  screws  for 

steel  panel  mounting  or  to  terminal  studs  fur<> 

nished  with  the  relay  for  ebony-asbestos  or 

slate  panel  mounting. 

The  terminal  studs  may 

be  easily  removed  or  inserted  by  locking  two 

nuts  on  the  studs  and  then  turning  the  proper 
nut  with  a  wrench. 

SETTINGS 

There  are  two  settings 

namely,  the  tap 

value  and  the  time  dial  settings. 

For  the 

protection  of  generators  from  excessive  nega­

tive  sequence  currents, 

the  settings  must  be 

determined  by  the  type  of  machine  and  the  full 
load  current  rating  of  the  machine. 

Tap  Value  Setting 

This  setting  is  determined  by  the  full  load 

current  of  the  generator  expressed  in  current 
transformer  secondary  amperes. 

Time  Dial  Setting 

Settings  of  the  time  dial  are  determined  by 

the  type  of  machine  to  be  protected. 

The  time 

dial  indicates  a  I

curve  of  a  generator 

for  which  the  relay  protects. 

By  turning  the 

time  dial,  the  relay  can  be  used  to  protect 
generators  with  I

T  constants  varying 

from 

"30"  to  "90"  as  shown  in  Fig.  3. 

ADJUSTMENTS  AND  MAINTENANCE 

All  the  relays  should  be 

inspected 

peri-

odically  and  the  time  of  operation  should  be 
checked  at  least  once  every  six  months  or  at 
such  other  time  intervals  as  may  be  dictated 

by  experience  to  be  suitable  to  the  particular 

application. 

Phantom  loads  should  not  be  used 

in  testing  induction-�ype  relays  because  of 
the  resulting  distorted  current  wave 

form 

which  produces  an  error  in  timing. 

All  contacts  should  be  cleaned  periodically. 

contact  burnisher  S#l82A836H01  llirecommended 

for  this  purpose.  The  use  of  abrasive  material 
for  cleaning  contacts  is  not  recommended,  be­
cause  of  the  danger  of  embedding  small  parti­
cles 

in 

the  face  of  the  soft  silver  and  thus 

impairing  the  contact. 

The  proper  adjustments  to  insure  correct 

operation  of  this  relay  have  been  made  at  the 

factory  and  should 

not  require 

after  receipt  by  the  customer. 

readjustment 

If  the  adjust-

ments  have  been  changed  or  the  relay  taken 

apart  for  repairs, 

the  instructions 

should  be  followed. 

below 

Adjust  the  stationary  contact  by  means  of 

its  adjusting  screw  such  that  the 

contact 

spring  is  just  free  of  the  front  spring  stop. 

By  means  of  the  time  dial, 

move  the 

moving 

contacts  until  they  deflect  the 

stationary 

contacts  approximately  1/64  inch. 

Set  the 

index  pointer  such  that  it  points  to  the  "O" 
mark  on  the  time  dial. 

Adjust  the  stationary 

contact  by  means  of  its  adjusting  screw  until 
the  moving  and  stationary  contacts  just  touch. 

This  adjustment  is  to  set  "O"  on  the  time  dial 

and  provide  follow  for  the  contacts. 

-

www 

. ElectricalPartManuals 

. com 

Содержание COQ Series

Страница 1: ...end and a pin and olive bearing on the upper end Both shaft bearings as well SUPERSEDES I L 41 277A 4 enotes changed from superseded issue as their 2djustable pins are removable A set screw and nylon plug locks the bottom pin in position and a sho lder nut of the time dial locks the top pin in position Attached to an insulated section of the disc shaft is a rigid arm holding a small silver hemisph...

Страница 2: ... generator characteristic at l per unit nega tive sequence current but at higher values of negative sequence current the relay charac teristic is substantially parallel and slight ly less than the generator characteristic In this manner a suitable margin of safety is obtained between the two characteristics Figure 2 defines the relay characteristics for two generators one with a permissible consta...

Страница 3: ...RACTERISTICS TIME DIAL 3 f SET J II 2 5 2 1 5 1 r i GENERATORS CHARACTERISTIC 12 2T 30 2 12 T 30 _ 1 t I 1 s 6 7 8 9 1 0 1 5 2 2 5 3 4 5 6 7 8 9 10 NEGATIVE SEQUENCE CURRENT IN PER UNIT 1 0 PER UNIT TAP VALUE CURRENT Fiq 2 Comparison 0 Relay Characteristic With Generator Characteristic 27 D 554 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 4: ...w w 1 z u w J cr 50 _j I u I I I v I 0 rr i 0 I cr 40 w z J w I l l lJ J I I 30 z I I I J I I 0 lL 0 w n 0 20 J 0 u f _j 0 1 0 10 z 0 w f 2 3 4 5 6 7 8 9 10 II TIME DIAL SETTING 27 D 5609 Fig 3 Tirne Dial Setting Versus Permissible Constant Of Generator 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 5: ...5 20 15 10 9 8 7 6 5 4 3 2 5 2 1 5 TIME DIAL SETTING 6 _ 1 l 1 l t I 5 6 7 8 9 1 0 1 5 2 2 5 3 4 5 6 7 8 9 10 NEGATIVE SEQUENCE CURRENT IN PER UNIT 1 0 PER UNIT TAP VALUE CURRENT Fig 4 Typical Operating Curves Of The COO Relay 27 D 5544 5 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 6: ...o be protected The time dial indicates a I T K curve of a generator for which the relay protects By turning the time dial the relay can be used to protect generators with I T constants varying from 30 to 90 as shown in Fig 3 ADJUSTMENTS AND MAINTENANCE All the relays should be inspected peri odically and the time of operation should be checked at least once every six months or at such other time i...

Страница 7: ...f the test connections is shown in Fig 6 Next adjust the spring tension until the relay will close contacts in 90 seconds with 5 2 ampe re s single per unit negative between terminals 8 phase tap value or one sequence current applied and 14 This adjustment is made by means of the spiral spring ad juster All spring convolutions must be free TRIP CIRCUIT Universal Trip This combination uses a 2 0 am...

Страница 8: ... RESPONSE TO ZERO SEQUENCE 27 D 5445 Fig 5 Diagram Of Test Connections Of The Type COO Relay For Adjusting Filter To Have No Response To Zero Sequence 8 ordering parts always give the complete name plate data ENERGY REQUIREMENTS The burdens of the type COQ Relay are as follows Watts Volt Amps Power Factor at 5 Amps at 5 Amps Angle 5 3 5 3 00 0 0 98 90 Lag 4 0 7 25 56 Lag TIMER STOPS 10 s i ER 3v o...

Страница 9: ... 0 92 TlltM tCKif w l U leQ 32 STVD FOR PI HEL LOCATION TM CK PANI L MTG FOR PRo JECTION ____ T fPE MTC 1 Olti J KR INT RNALSCH CUT OUT r Q SEHI FLUSH MOUNTING 0 rt2l j M TIC f Otl JEt r c GON_ T _ c rit c JTOUTl OR P1 0J CT ON MTC T IN PI NEI I PANEL I OCA1 0trrl FOR SEMI FW ot TVPE I m Fig 9 0utline And Drilling Plan Of The MlO Projection Or Semi Flush FT Flexitest Case 16 B 2477 9 w w w E l e c...

Страница 10: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 11: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 12: ...WESTINGHOUSE ELECTRIC CORPORATION METER DIVISION NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Отзывы: