Remote RMM-700 Installation Guide
Installation
1-800-377-8766
Page 15
and earthing electrode conductor. The DC system cannot be earthed
elsewhere.
The DC power source must be located in the same premises as the chassis.
No switching or disconnecting devices can occur between the earthed
conductor of the DC source and the earthing electrode conductor.
Step 5: Connect DC Power Input
WARNING:
Turn off the power feed before connecting wires.
Connect the input power feed to the power supply connector. Be careful to observe
polarity.
To connect wires:
1. Turn off power feed.
2. Strip ends of wire 5/16 in. (7 mm).
3. (optional) Using a small flathead screwdriver, loosen screws on sides of power
connector on the bottom right front of Remote RMM-700.
4. (optional) Remove power connector.
5. Insert wire into connector and tighten screws.
Notes:
For ground connection,
use 14AWG or larger
conductor.
Apply an appropriate antioxidant to
the bare conductors before crimping
the connector to the connector
mating surface.
A readily accessible disconnect
device (suitably approved and
rated) must be incorporated in
the field wiring.
Caution:
Unscrew these two screws to remove the
power connector, if necessary.