background image

Section BXM‐301‐10H‐20A

030‐101901 Rev. A

R

11

1608IARA

Figure 16. Ground Plate of Boxer‐30 Cabinet

ESD jack

Ground

Lug

Earth

8 sets of posts for

bonding cables

and equipment

9.

Drill bottom mounting holes. 

Drill appropriately‐sized pi­

lot holes, slightly smaller than the width and depth of the
bolts, for the lower mounting bracket. Use a minimum of
three bolts. 

Do not drill the holes too large.

10.

Install bottom mounting bolts.

 Insert and drive all bottom

bolts completely in to their final seated position. Finish
the installation by verifying all bolts are firm and snug.

11.

Determine next step.

 If ground, power, and communica­

tions cables and internal equipment will not be connected,
installed or mounted at this time, proceed to the next step
to finalize the cabinet installation. If ground, power, and
communications cables and internal equipment will be
connected, mounted, and powered‐up at this time, skip
the next step and proceed to Paragraphs 3.7 through Para­
graph 3.16 for those procedures.

12.

Close up cabinet and clean the site.

 Close the Boxer‐30

door, and lock it using a can wrench or 216 tool and an op­
tional padlock. Pick up any tools and materials at the
installation site, and clean the site of any trash or debris.

‐ NOTE ‐

Always follow local safety precautions and standard operating
procedures for grounding the equipment when installing, up­
grading, repairing or maintaining equipment. Any instructions or
information contained herein is subordinate to local codes, oper­
ating procedures or practices.

3.7

Making Ground Connections

Eight sets of bond/ground posts, a ground lug, and an ESD jack
are provided on a ground plate on the interior floor of the cabi­
net (see Figure 16). The posts are provided to bond both
network and customer equipment or communications cables.
An external earth ground rod or wire (#6 AWG) must enter the
cabinet and be connected to the ground lug located on the inte­
rior ground plate. 

Make all ground connections prior to any

telecommunications cable connections.

1.

Locate or establish an external earth ground. 

Find or

create an external and appropriate earth ground, per com­
pany practice and local codes.

2.

Remove a knock‐out for the earth ground wire. 

Per compa­

ny practice, determine which cabinet knock‐out hole
location should be used for earth ground wire entrance (a
small forward knock‐out is recommended). If not already
removed, remove the selected knock‐out.

3.

Install a rubber grommet or liquid‐tight fitting.

 Install ei­

ther conduit and an appropriate and liquid‐tight fitting or
a rubber grommet in the knock‐out hole.

4.

Route ground wire through knock‐out hole. 

Run the ap­

proved ground wire through the grommet or conduit to
the ground lug.

5.

Connect earth ground wire. 

Connect the earth ground

wire to the #6 AWG ground lug on the ground plate, per
company practice.

6.

Seal the earth ground entrance hole.

 Depending on the

type of fitting or grommet used, it may be necessary to seal
the ground wire entrance hole, as stated in the note below.

‐ NOTE ‐

To improve the integrity of the cable entries seal when rubber
grommets are used, a water‐proof foam or silicone sealant
should be used on the interior side of the cabinet, around the ex­
posed grommet and cable entry.

7.

Ground installed equipment and cables.

 As each cable and

piece of equipment is mounted inside the cabinet (in the
following sections), connect it to a ground lug or post pro­
vided on the ground plate, per company practice.

8.

Use ESD ground jack.

 Whenever installing equipment or

performing system testing or maintenance, use the pro­
vided ESD ground jack also provided on the cabinet's
interior ground plate.

3.8

Making Fan Power Connections

To power the factory‐prewired Boxer‐30 cooling fans, an exter­
nal ‐48VDC (4.9A) power source must be connected to the
power cable of the heat exchanger.

‐ NOTE ‐

Ensure that the power source has sufficient power to support the
235 watts required to operate the Boxer‐30 fans plus the power
required for the telecommunications equipment that is being
installed in the cabinet.

‐ NOTE ‐

Boxer requires ‐48VDC @ 4.9A to operate.

Connecting ‐48VDC Fan Power

Follow the steps below to connect ‐48VDC fan power from a
‐48VDC power source to the blunt‐cut power cord for the heat
exchanger compartment. Always follow local codes and com­
pany practices.

1.

Verify the power source.

 Verify the power source is in good

working condition.

2.

Remove or disable power.

 Disable power at the power

source before proceeding (power is re‐applied later).

3.

Remove knock‐out for power wires.

 Select the best knock‐

out for power cable ingress and egress, and remove the
knock‐out per Paragraph 3.5, and prepare any grommet
placement and conduit fittings per company practice.

4.

Route wires into cabinet.

 Extend and route the DC wires

from the ‐48VDC power source into the Boxer‐30 cabinet
through the knock‐out hole. Allow enough wire to reach
an optional field‐provided rectifier, with sufficient slack.

5.

Strip power wires.

 Remove approximately 5” of jacket

from the power cord, then strip off approximately 3/16”
from the end of the wires for DC power.

Содержание A90-BXM3019-10HE

Страница 1: ...3 Product Purpose and Description Boxer 30 is an actively cooled NEMA 4 outdoor cabinet that can house and protect a wide range of electronic equipment Up to 30 vertical RUs 52 5 of 19 inch wide inter...

Страница 2: ...t shown ware must be capable of supporting the weight of the Boxer 30 cabinet plus the weight of any equipment mounted in it The Boxer 30 cabinet is typically located at the customer premises but can...

Страница 3: ...nting brackets at the top and bottom of the cabinet facilitate wall and H frame mount ing The bottom floor of the main cabinet contains numerous differently sized intact knock outs Paragraph 2 1 2 6 t...

Страница 4: ...kets one at the top and one at the bottom of the cabinet come factory installed Figure 7 Mounting Brackets for Wall H Frame Mounting Top Exterior Mounting Bracket note the keyholes Bottom Exterior Mou...

Страница 5: ...moved forward 2 or backward 3 if a few additional inches of equipment depth is needed at either the front or back of the channel Seven slots are provided for seven channel positions see Figure 2 Each...

Страница 6: ...internal temperature reaches 70_F 21 1_C and will reach full speed when the internal tem perature reaches 80_F 26 7_C The external heat exchanger fan will turn on at 10 speed when the external temper...

Страница 7: ...ro vided E This product should be operated only from the type of power source indicated on the marking label F Never push objects of any kind into this product through cabi net slots as they may touch...

Страница 8: ...ut type and regardless of the order of the mounting steps All knock outs should be knocked out from the inside of the cabinet except for the small 0 575 knock outs which are to be knocked out from the...

Страница 9: ...ttom mounting bracket and H frame rail Verify the cabinet is in the proper horizontal position make any needed ad justments then securely tighten all mounting hardware 6 Test installation firmness Tes...

Страница 10: ...cabinet then marking the mounting hole loca tions or by measuring without lifting the equipment as a template Two of the mounting bracket holes are 16 apart on centers to facilitate mounting on standa...

Страница 11: ...met or liquid tight fitting Install ei ther conduit and an appropriate and liquid tight fitting or a rubber grommet in the knock out hole 4 Route ground wire through knock out hole Run the ap proved g...

Страница 12: ...applied in Para graph 3 12 3 Verify the knock outs are removed Perform the steps in Paragraph 3 5 to remove any appropriate cabinet hole knock out s and to install an appropriate fitting or grom met...

Страница 13: ...laced inside the cabinet does not exceed the maximum weight requirement for the mounting structure surface and type 4 Determine the best mounting location for each piece of equipment for maximum capac...

Страница 14: ...ble 2 for the replacement heat exchanger part number Figure 20 Field Replacement of Heat Exchanger Location of top two nuts Location of four lower bolts Heat exchanger Hole for AC power cord 1 4 20 1...

Страница 15: ...er from Westell Once an RMA number is obtained return the defec tive unit freight prepaid and a brief problem description to Voice 630 375 4457 email rgmdept westell com Replacements will be shipped i...

Страница 16: ...ncy Specifications The Boxer 30 cabinet is designed to meet the following regula tory safety or environmental specifications or requirements S NEMA 4 compliant 9 APPENDIX A PRODUCT VIEWS Figure 21 Bot...

Страница 17: ...Section BXM 301 10H 20A 030 101901 Rev A R 17 1608IARA Figure 22 Front Exterior View of Boxer 30 Cabinet 35 4 60 6 24 4 24 0 56 8 17 8 2 0 18 4 Top and bottom mounting brackets not shown...

Страница 18: ...Section BXM 301 10H 20A 030 101901 Rev A R 18 1608IARA 18 3 21 3 29 6 60 6 56 8 Figure 23 Exterior Right Side View of Boxer 30 Cabinet Top and bottom mounting brackets not shown...

Отзывы: