39
Job1, Job2: When an event occurs, the task to be performed is called the job. A typical
example is to trigger an alarm buzzer in event of high temperature. Each pen can accept four
events ( or alarms ) and each event can create two jobs. Please note that a job under Event is
different from a job by pressing the Operate key. The former is actuated by an event, and the
latter is actuated by manual control, no event necessary.
Various types of jobs can be selected:
No Action: Do nothing.
Log Alarm: Record alarms
Log Event: Record events
Stop logging: Stop logging data.
Start logging: Start logging data.
Sound Buzzer: Sound the buzzer. It stops once any key is pressed.
DO Latch On: Set digital output / relay on, and then select Target from DO 1 to DO 6. The
relay is latched when it is activated.
DO Latch Off: Set digital output / relay off, and then select Target from DO 1 to DO 6. The
relay is latched when it is activated.
DO Process: Set digital output / relay on for process high or low, and then select Target from
DO 1 to DO 6. The relay is not going to be latched when it is activated.
Enable Timer: Start the timer, and then select Target from Timer 1 to Timer 6.
Disable Timer: Stop the timer, and then select Target from Timer 1 to Timer 6.
Preset Totalz: Start the totalizer with a preset value, then select Target from Tolz 1 to Tolz 6.
Reset Totalz: Reset totalizer into zero, and then select Target from Tolz 1 to Tolz 6.
Enable Totalz: Start the totalizer, then select Target from Tolz 1 to Tolz 6.
Disable Totalz: Stop the totalizer, then select Target from Tolz 1 to Tolz 6.
Preset Counter: Start the Counter with a preset value, then select Target from Cont1 to Cont6.
Reset Counter: Resets the counter into zero, and then select Target from Cont1 to Cont6.
Inc Counter: Increase the counter, and then select Target from Cont1 to Cont6.
Dec Counter: Decrease the counter, and then select Target from Cont1 to Cont6.
Log Report: Make the report for Counter and Totalizer. Choose this column, and then the
report will be presented as details described in 3.4 Event.
Reset MinMaxAve: In Report function, after logging the MinMaxAve data of AI and Math
channels for one day for example, then reset historical data in order to logging new data
for the next day.
Hysteresis: To avoid it been activated too often, the relay can set for no reaction in 0.1% to 10%
of full span ( Low Scale to High Scale ).
Note:
The sampling rate of the recorder is fixed at 200 milli seconds by the hardware, i.e. samples
5 measured data per second.. If the logging speed is set at 1 second in Instant mode, the
recorder logs using the last of five measured data values. For the same speed in Averaging
mode, the recorder logs using the average of the five measured data values. For the same
speed in the Maximum or Minimum mode, then the recorder logs using the maximum or
minimum of the five measured data values..
Sampling Logging ( historical trend ) Display ( real time )
Instant 200mS the last of 5 measured data the last of 5 measured data
Averaged 200mS the average of 5 measured data the last of 5 measured data
Maximum 200mS the maximum of 5 measured data the last of 5 measured data
Minimum 200mS the minimum of 5 measured data the last of 5 measured data
Содержание WH18/06
Страница 1: ...User Manual Paperless Recorder WH18 06 15th Edition 03 2008 ...
Страница 17: ...17 Figure 2 6 Figure 2 7 Figure 2 8 ...
Страница 19: ...19 Figure 2 10 Figure 2 11 ...
Страница 25: ...25 Digital input card DI181 Figure 2 21 Analog output card AO183I AO183V Figure 2 22 ...
Страница 26: ...26 24 VDC auxiliary power supply card AP181 Figure 2 23 2 5 RS 232 RS 422 RS 485 wiring Figure 2 24 ...
Страница 27: ...27 Figure 2 25 Figure 2 26 ...
Страница 70: ...70 Make sure that RS 232 communication setting at the recorder and PC are equal ...
Страница 87: ...87 7 Trouble shooting ...
Страница 88: ...88 ...
Страница 89: ...89 ...
Страница 90: ...90 ...