23
2.4 Wiring of the cards
Wiring Precautions
1. Care must be taken to ensure that maximum voltage rating specified on the label is not
exceeded.
2. For the panel-mount version, it is recommended that near the equipment an external fuse and
an external switch rated at 2A/250 VAC should be equipped.
3. Beware not to over tighten the terminals screws. The torque should not exceed 0.7 N-m
( 6.3 Lb-in or 7.1 Kg F-cm ).
4. Except the thermocouple wirings, all wirings should be stranded copper conductor with
maximum gauge 18 AWG.
5. Connect a grounding conductor with 1.6mm diameter minimum to provide protective
grounding prior to turning on the equipment.
Rear terminals
Figure 2 –17
Note:
▲
The six rear Slots can be inserted only by six cards in maximum. It can be either
input card, output card or 24 VDC auxiliary power supply card.