Meaning of parameters
All inputs and outputs for individual milking plant components can be tested in the
parameter level. To this end, the corresponding relays should be set to 'I' or '0'. However,
the two relays for intake of acidic and alkaline detergents are locked against each other, to
prevent acidic and alkaline detergents entering at the same time.
Test output relay
Setting range
Factory setting
Select parameter using UP/DOWN. Hold down SET: UP=on DOWN=off
t1 Test relay output 1 cold water valve
0..1
0
t2 Test relay output 2 warm water valve
0..1
0
t3 Test relay output 3 alkaline
0..1
0
t4 Test relay output 4 acid
0..1
0
(t3 and t4 are locked against each other)
t5 Test relay output 5 drain valve
0..1
0
t6 Test relay output 6 vacuum pump
0..1
0
t7 Test relay output 7 heater
0..1
0
t8 Test relay output 8 air injektor
0..1
0
t9 Test relay output 9 adjustable
0..1
0
t10 Test relay output 10 adjustable
0..1
0
t11 Test relay output 11 adjustable
0..1
0
t12 Test relay output 12 drain valve
0..1
0
Test inputs
Setting range
Factory setting
Press SET: Input connected = 1, Input not connected = 0
t14 Test input Niveau
0..1
-
t15 Test input 1 milking
0..1
-
t16 Test input 2 safety switch
0..1
-
t17 Test input 3 Start from Stop
0..1
-
t18 Test input 4 Dry-running protection
0..1
-
t19 Test input 5 Water intake during circulation
0..1
-
t20 Test input 6 (not used yet)
0..1
-
WMS-100 104193 V2.7 - 14.10.2019
Operation of the level “Service parameters”
Switch to level “Service parameters”
!
See page 23.
t-Parameters
Page 32
Working level
for normal daily operation
Code 471
Code 454
Code 382
Code 567
Cleaning parameter
Configuration
(E-parameters)
Cleaning parameter
running times
(P-parameters)
Service parameters
(t-parameters)
User-defined
cleaning functions
(b-parameters)