5. Operation
104781 - MRF-2 | MRH-2 - V2.4 - 22.07.2020
Page 35
5.8.3 H- parameter (option level)
Description
Range
Default
H1
H2
Kind of temperature alarm 1
Kind of temperature alarm 2
0 .. 5
0 .. 5
0
0
When an alarm with relative limits is selected, the parameter values set for the upper and
lower alarm limits always relate to the assigned setpoint.
0:
Limit value alarm with relative limits in relation to setpoint
1:
Limit value alarm with absolute limits
2:
High temperature alarm with relative limits in relation to setpoint
3:
High temperature alarm with absolute limits
4:
Low temperature alarm with relative limits in relation to setpoint
5:
Low temperature alarm with absolute limits
Optional: In the event of an alarm, the analog output is limited to the maximum value set in
D17.
6:
as 0, but with analog output limitation in case of alarm
7:
as 1, but with analog output limitation in case of alarm
8:
as 2, but with analog output limitation in case of alarm
9:
as 3, but with analog output limitation in case of alarm
10:
as 4, but with analog output limitation in case of alarm
11:
as 5, but with analog output limitation in case of alarm
H3
H4
Assignment temperature alarm 1
Assignment temperature alarm 2
0 .. 4
0 .. 4
0
0
0:
disabled
1 ..4:
Connected to controller block 1 .. 4
H5
H6
Special function temperature alarm 1
Special function temperature alarm 2
0 .. 63
0 .. 63
0
0
A temperature alarm directly switches off the relays stipulated according to the following
table. The setting 32' means that only the fault report component is enabled.
Val.
0:
1:
2:
3:
4:
5:
6:
7:
8:
9:
10:
11:
12:
13:
14:
15:
16:
17:
18:
19:
20:
21:
22:
23:
24:
25:
26:
27:
28:
29:
30:
31:
STM
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
K5
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
K4
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
K3
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
K2
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
K1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
Val.
32:
33:
34:
35:
36:
37:
38:
39:
40:
41:
42:
43:
44:
45:
46:
47:
48:
49:
50:
51:
52:
53:
54:
55:
56:
57:
58:
59:
60:
61:
62:
63:
STM
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
K5
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
K4
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
K3
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
K2
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
K1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0:
no influence
1:
Switch off the relay in a force-guided manner
or send a message to the fault message block
NB:
Full list of parameters.
Depending on control-
ler type and parameter
configuration, certain
parameters may be
hidden.