5. Operation
Page 36
104781 - MRF-2 | MRH-2 - V2.4 - 22.07.2020
Description
Range
Default
H7
H8
Hysteresis temperature alarm 1
Hysteresis temperature alarm 2
0,1 .. 5K
0,1 .. 5K
0,1
0,1
H9
H10
Switch-on delay temperature alarm 1
Switch-on delay temperature alarm 2
0 .. 999 sec.
0 .. 999 sec.
0
0
Period for which alarm event must exist for alarm to be triggered.
H11
H12
Activation delay for temperature alarm 1*
Activation delay for temperature alarm 2*
0 .. 300 min.
0 .. 300 min.
0
0
* after mains power on
H13
Temperature alarm 1 display
0 .. 1
0
0 =
no text
1 =
display alternates between “AL1" and the alarm temperature assigned in [H3].
If alarm temperature 2 is also reached, ONLY “AL2" appears in the display!
H14
Temperature alarm 2 display (dominant)
0 .. 1
0
0 =
no text
1 =
display alternates between “AL2" and the alarm temperature assigned in [H4].
H21
H22
H23
H24
H25
Function digital input 1
Function digital input 2
Function digital input 3
Function digital input 4
Function digital input 5
0 .. 67
0 .. 67
0 .. 67
0 .. 67
0 .. 67
0
0
0
0
0
Val.
0:
1:
2:
3:
4:
5:
6:
7:
8:
9:
10:
11:
12:
13:
14:
15:
16:
17:
18:
19:
20:
21:
22:
23:
24:
25:
26:
27:
28:
29:
30:
31:
STM
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
K5
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
K4
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
K3
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
K2
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
K1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
Val.
32:
33:
34:
35:
36:
37:
38:
39:
40:
41:
42:
43:
44:
45:
46:
47:
48:
49:
50:
51:
52:
53:
54:
55:
56:
57:
58:
59:
60:
61:
62:
63:
STM
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
K5
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
K4
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
K3
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
K2
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
K1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
„0“ means: input disabled
„1“ means: Switch off relay forcibly or alarm on fault report component
64:
Switchover to alternative setpoint C6
65:
Standby as long as input active
66:
Relay direct, off during standby
67:
Relay direct, regardless of standby
68:
Limitation analog output. (Output is limited to D17)