Installation and operating instruction
Dual fuel burner WGL30/1-C ZM
9 Servicing
83260202 1/2019-02 La
86-144
9.4 Set mixing head
Observe notes on servicing [ch. 9.1].
Dimension L1 and Lx changes according to the combustion head extension used.
Set nozzle distance
Insert setting gauge and check dimension A (5 … 6 mm).
If the value measured deviates from dimension A:
Remove nozzle assembly [ch. 9.5].
Check dimension L1 and if necessary adjust by moving the carrier
1
.
L1 = 313 mm
W3
0/2
A = 5 ... 6 mm
1
Check basic setting
Turn setting screw
1
until the indicating bolt
2
is flush with the nozzle as-
sembly cover (dimension X = 0 mm).
Check dimension Lx.
If the value measured deviates from dimension Lx:
Check position of diffuser [ch. 9.7].
If the measured value still deviates:
Set dimension Lx by turning the setting screw
1
.
Remove plug from indicating bolt
2
.
Turn indicating bolt until it is flush with the nozzle assembly cover
(dimension X = 0 mm).
Replace plug.
Lx = 4
00 mm
X
1
2
Содержание WGL30/1-C ZM
Страница 1: ...Installation and operating instruction Dual fuel burner WGL30 1 C ZM 83260202 1 2019 02 ...
Страница 121: ...Installation and operating instruction Dual fuel burner WGL30 1 C ZM 12 Project planning 83260202 1 2019 02 La 121 144 ...
Страница 138: ...Installation and operating instruction Dual fuel burner WGL30 1 C ZM 14 Notes 83260202 1 2019 02 La 138 144 14 Notes ...
Страница 139: ...Installation and operating instruction Dual fuel burner WGL30 1 C ZM 14 Notes 83260202 1 2019 02 La 139 144 ...
Страница 143: ...83260202 1 2019 02 La ...