Installation and operating instruction
Dual fuel burner WGL30/1-C ZM
7 Commissioning
83260202 1/2019-02 La
53-144
7.1.3 Check gas connection pressure
Minimum connection pressure
Add the combustion chamber pressure in mbar to the minimum connection pres-
sure. The connection pressure should not fall below 15 mbar.
Determine minimum connection pressure for low pressure installations from table
[ch. 7.1.6].
Maximum connection pressure
Maximum connection pressure into isolating valve is 300 mbar.
Check connection pressure
DANGER
Risk of explosion due to excess gas supply pressure
Exceeding the maximum connection pressure (see name plate) can damage the
gas valve train and lead to an explosion.
Max. connection pressure see name plate.
Check gas connection pressure
Only in conjunction with W-MF and gas connection pressure > 150 mbar
The pressure measuring device must be connected to the pressure regulator.
Check gas connection pressure, see additional sheet (print No. 835109xx).
Connect pressure measuring device to test point
1
.
Slowly open isolating valve whilst observing the pressure increase.
If the connection pressure exceeds the max. connection pressure:
Immediately close isolating valve.
Do not start plant.
Notify system operator.
If the connection pressure does not maintain the min. connection pressure:
Do not start plant.
Notify system operator.
1
Содержание WGL30/1-C ZM
Страница 1: ...Installation and operating instruction Dual fuel burner WGL30 1 C ZM 83260202 1 2019 02 ...
Страница 121: ...Installation and operating instruction Dual fuel burner WGL30 1 C ZM 12 Project planning 83260202 1 2019 02 La 121 144 ...
Страница 138: ...Installation and operating instruction Dual fuel burner WGL30 1 C ZM 14 Notes 83260202 1 2019 02 La 138 144 14 Notes ...
Страница 139: ...Installation and operating instruction Dual fuel burner WGL30 1 C ZM 14 Notes 83260202 1 2019 02 La 139 144 ...
Страница 143: ...83260202 1 2019 02 La ...