Installation and operating instruction
Dual fuel burner WGL30/1-C ZM
6 Operation
83260202 1/2019-02 La
47-144
Pno.
Parameters
Setting range
Factory
setting
C
Operating mode output X3:1
for gas operation
0
: not activated
1
: with pilot valve not interrupted
2
: with pilot valve interrupted
3
: Standard (external LPG valve)
3
d
Flame sensor
0
: ionisation electrode / flame sensor FLW
1
: switch input (X3:14)
2
: flame sensor QRB
0
E
Display mode
0
: E-parameter is not activated in the access level
1
: E-parameter is activated in the access level
Settings
2
and
3
are required for O
2
trim, see supplementary
sheet O
2
trim W burners (Print No. 835587xx).
0
F
Restart attempts following
flame failure
0
…
1
1
H
Actuator setting for post-purge
0.0
…
90.0
°
Change air damper setting:
Press [L/A] and [+] or [–].
0
L
Load shutdown
0.0
…
4095
seconds
If there is no longer a demand for heat, the W-FM reduces
the burner capacity and closes the fuel valves after the time
set has elapsed. If partial load is reached before the time
has elapsed, the fuel valves close immediately.
0
n
Operating mode O
2
trim gas
operation (only in conjunction
with O
2
trim)
0
: not activated
Additional parameters can be displayed with setting
1
…
4
,
see supplementary sheet O
2
trim W burners
(Print No. 83yyyyxx).
0
o
Operating mode O
2
trim oil op-
eration (only in conjunction with
O
2
trim)
0
: not activated
Additional parameters can be displayed with setting
1
…
4
,
see supplementary sheet O
2
trim W burners
(Print No. 835587xx).
0
After the last parameter or a waiting time of approx. 20 seconds the combustion
manager changes over to the operating level.
Содержание WGL30/1-C ZM
Страница 1: ...Installation and operating instruction Dual fuel burner WGL30 1 C ZM 83260202 1 2019 02 ...
Страница 121: ...Installation and operating instruction Dual fuel burner WGL30 1 C ZM 12 Project planning 83260202 1 2019 02 La 121 144 ...
Страница 138: ...Installation and operating instruction Dual fuel burner WGL30 1 C ZM 14 Notes 83260202 1 2019 02 La 138 144 14 Notes ...
Страница 139: ...Installation and operating instruction Dual fuel burner WGL30 1 C ZM 14 Notes 83260202 1 2019 02 La 139 144 ...
Страница 143: ...83260202 1 2019 02 La ...