![Weishaupt WG20-/1-C LN Series Скачать руководство пользователя страница 52](http://html.mh-extra.com/html/weishaupt/wg20-1-c-ln-series/wg20-1-c-ln-series_manual_953381052.webp)
Installation and operating instruction
Gas burner WG20…/1-C LN
9 Servicing
83240802 1/2020-01 La
52-96
9.3 Removing and refitting mixing head
Observe notes on servicing [ch. 9.1].
DANGER
Risk of explosion due to leaking gas
It is possible for gas to leak out if the gasket
3
is seated incorrectly.
Following work on the mixing head, ensure the gasket is clean and seated cor-
rectly, if necessary replace.
Check for leaks, see Fourth test phase [ch. 7.1.3].
Removing
Unplug ionisation cable
5
.
Unplug ignition cable
1
.
Undo screws
4
.
Turn mixing head
2
to the left up to the recess and remove.
Refitting
Refit mixing head in reverse order ensuring correct alignment and cleanliness of
gasket
3
.
1
4
2
3
5