![Weishaupt WG20-/1-C LN Series Скачать руководство пользователя страница 38](http://html.mh-extra.com/html/weishaupt/wg20-1-c-ln-series/wg20-1-c-ln-series_manual_953381038.webp)
Installation and operating instruction
Gas burner WG20…/1-C LN
7 Commissioning
83240802 1/2020-01 La
38-96
Preset setting pressure
Only in conjunction with W-MF and gas connection pressure > 150 mbar
The pre-pressure must be set to approx. 90 mbar.
Set FRS pressure regulator, see additional sheet (print No. 835109xx).
Pre-set setting pressure determined for ignition load
2
and full load
1
at multi-
function assembly.
1
2
Setting
Factory presetting
1
Full load
7 mbar
2
Ignition load
4 mbar
The transition from ignition load to full load is carried out sliding.