![Weishaupt WG20-/1-C LN Series Скачать руководство пользователя страница 17](http://html.mh-extra.com/html/weishaupt/wg20-1-c-ln-series/wg20-1-c-ln-series_manual_953381017.webp)
Installation and operating instruction
Gas burner WG20…/1-C LN
3 Product description
83240802 1/2020-01 La
17-96
3.4.5 Emissions
Flue gas
To EN 676 the burner complies with emission class 3.
The NO
x
values are influenced by:
combustion chamber dimensions
flue gas system
fuel
combustion air (temperature and humidity)
medium temperature
Combustion chamber dimensions, see Weishaupt Partner Portal / Documents and
Applications / Online Applications / NO
X
calculation for burners.
Sound levels
Dual number noise emission values
Measured sound power level L
WA
(re 1 pW)
Uncertainty value K
WA
78
4
dB(A)
(1
dB(A)
Measured sound pressure level L
pA
(re 20 μPa)
Uncertainty value K
pA
73
4
dB(A)
(2
dB(A)
(1
Determined to ISO 9614-2.
(2
Determined at 1 metre distance from the front of the burner.
The measured noise levels plus uncertainty values form the upper limit value, which
could occur when measuring.
Содержание WG20-/1-C LN Series
Страница 1: ...Installation and operating instruction Gas burner WG20 1 C LN 83240802 1 2020 01 ...
Страница 90: ...Installation and operating instruction Gas burner WG20 1 C LN 14 Notes 83240802 1 2020 01 La 90 96 14 Notes ...
Страница 91: ...Installation and operating instruction Gas burner WG20 1 C LN 14 Notes 83240802 1 2020 01 La 91 96 ...
Страница 92: ...Installation and operating instruction Gas burner WG20 1 C LN 14 Notes 83240802 1 2020 01 La 92 96 ...
Страница 95: ...83240802 1 2020 01 La ...