60
Cause and rectification of faults
9
Table of fault and warning message:
Most irregularities and faults of the boiler are recognised
by the WCM and shown on the display. The display dif-
ferentiates between faults (boiler lockout) and warnings.
Faults
(crossed out flame signal flashes)
Proceed as follows with
faults
:
•
Note down the fault displayed (flashing)
•
Press reset key
Warning
With
warnings
the boiler does not lock out.
The warning is shown in the display and expires by
itself once the cause of the warning no longer exists.
CODE Message Cause
Possible
fault/rectification
Temperatures
11
Fault
Boiler temperature
≥
105°C
• No water in boiler - top up water
• Air in boiler - vent boiler
• No boiler throughput - check function of pump
12
Warning
Boiler temperature
≥
95°C
• No water in boiler - top up water
• Air in boiler - vent boiler
• No boiler throughput - check function of pump
13
Fault
Flue gas temperature
≥
120°C
• Heat exchanger heavily soiled
14
Warning
Flow temperature
• Air in boiler - vent boiler
gradient too large
• No boiler throughput
• System pressure too low
15
Warning /
Temperature difference between
• Heat exchanger through flow insufficient
fault
1)
boiler temperature and flue gas
temperature too high
16
Warning
Flue gas temperature
≥
115°C
• Heat exchanger heavily soiled
1)
After 30 consecutive warnings the boiler goes to
lockout.