© 2020 Weinzierl Engineering GmbH
Page 4/49
2.1 KNX programming mode
The KNX programming mode is activated/deactivated either by pressing the flushed KNX
programming button
❸
or by simultaneously pressing the buttons
❼
and
❽
. The operation of
the programming mode at the front can be activated/deactivated in the ETS® with Prog. mode on
device front.
When the programming mode is active, the programming LED
❷
and the LED Mode
❺
light up
red.
2.2 Manual operation and status display
The LED KNX
❹
lights up or flashes when KNX bus voltage is present.
The LED Mode
❺
lights up or flashes when KNX bus voltage is present.
The LED RTU
❻
lights up or flashes when supply voltage is present.
The synchronization of the KNX objects is triggered by pressing the button KNX
❼
for a long time.
This is indicated by the LED Mode
❺
lighting up in orange.
Pressing the button RTU
❽
for a long time triggers the synchronization of the Modbus registers.
This is indicated by the LED Mode
❺
lighting up in orange.
The LED KNX
❹
is used to indicate the status of KNX communication. It flashes when sending
and receiving telegrams.
The LED RTU
❻
indicates the status of the Modbus communication. It flashes when sending and
receiving telegrams.
Summary of the states of the LED Mode
❺
:
LED Status
Meaning
LED lights green
The unit operates in normal operating mode.
LED lights red
The programming mode is active.
LED lights orange
The programming mode is not active.
Synchronization is active.
LED flashes red
The programming mode is not active.
Synchronization is not active.
The device is not loaded correctly, e.g. after aborting a download.
LED flashes green
The device is currently loaded by the ETS.