Heartbeat
Cyclic sending of values to the KNX bus, to indicate that the device is operational. For the Cycle
time values between 1 min and 24 h are selectable.
Group object
Type KNX
Size
Direction
GO 277 Heartbeat
– Trigger
1.001
1 bit
To KNX
Telegram rate limitation
With this parameter the telegram rate limitation can be activated or deactivated.
Time telegram rate
If telegram rate limitation is activated, the time between the telegrams can be configured here.
Times between 0.1 sec. and 1.0 sec. can be selected.
The telegram rate limitation only occurs when the bus load is increased.
5.3 Modbus settings
KNX Gateway
This parameter defines the role of the KNX gateway within the client/server architecture of the
Modbus environment. Available are:
▪
Modbus master
▪
Modbus slave