Install burner
(also refer to instructions packed with
burner)
Use only burners specified for use on
Weil-McLain GOLD oil boilers. DO
NOT use burners specified for use on
Weil-McLain Model 68 boilers. Contact
individual burner manufacturers for
proper burner selections.
For P-SGO and A-SGO boiler:
1. Secure universal mounting flange and gasket to
burner mounting door. Use three bolts provided.
2. Secure burner on flange with three bolts.
3. Position burner so end of air tube is level to
1½-degree tilt down toward chamber. Open door
to verify burner position. End of air tube should be
flush to ¼" recessed from inside wall of burner door
refractory. Check for secure placement of insulation
on target wall, chamber floor and burner mounting
door. Securely close door.
General chimney requirements
•
Designed for natural draft firing. Connect boiler
to vertical chimney.
Insufficient draft can cause flue gas leak-
age and carbon monoxide emissions,
which will lead to severe personal injury
or death.
•
Use vent material approved by local codes for oil-
fired burners. In their absence, refer to:
•
NFPA 31, Installation of Oil-Burning Equip-
ment.
•
NFPA 211, Standard for Chimneys, Fireplaces,
Vents and Solid Fuel Burning Appliances.
•
In Canada, refer to CSA B139, Installation Code
for Oil-Burning Equipment.
•
NFPA 211 requires chimney to be lined before con-
nected to boiler.
Inspect existing chimney before installing new boiler. Failure
to do any of the following will result in severe personal injury
or death:
•
Clean chimney, including removal of blockage.
•
Repair or replace damaged pipe or liner.
•
Repair mortar and joints.
To prevent downdrafts, extend chimney at least 3 feet above highest point
where it passes through roof and 2 feet higher than any portion of building
within 10 feet. Increase chimney cross-sectional area and height at least
4% per 1,000 feet above sea level.
•
Minimum clearances from vent pipe to combustible material:
•
6 inches — Type “L” double-wall vent
•
9 inches — Single-wall vent
•
Minimum chimney sizes should be used.
Oversized chimneys, outside masonry chimneys and/or der-
ated inputs can result in condensation in chimney.
Boiler
model
number
Minimum
breeching
diameter
(Note 3)
Minimum I=B=R chimney
size
Minimum chimney
height
Rect.
Round
SGO-3
5"
8" x 8"
(Note 1)
6"
15'
SGO-4
6"
SGO-5
6"
8" x 8"
(Note 1)
7"
15'
SGO-6
7"
SGO-7
SGO-8
7"
8" x 12"
(Note 2)
7"
20'
SGO-9
Note 1
6¾" x 6¾" inside liner
Note 2
6½" x 10½" inside liner
Note 3
Flue collar on boiler is 7' diameter
Table 3
Minimum chimney sizes
Install burner — all boilers
Part number 550-141-829/1211
16
GOLD
SGO
OIL-FIRED NATURAL DRAFT STEAM BOILER — SERIES 3 —
Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.