Installations must comply with
•
United States
•
State and local plumbing, heating and electrical codes.
•
National codes where applicable.
•
Canada
•
Canadian Standards Association, CSA B139, Installation Code for
Oil-Burning Equipment.
•
CSA C22.1 Canadian Electrical Code Part One.
•
Applicable local or provincial codes.
Before selecting boiler location
•
Check for nearby connections to:
•
System water piping.
•
Chimney. See page 16. Boiler can be top or back vented.
•
Combustion and ventilation air supply. See page 10.
•
Oil supply. See page 30 for oil line routing.
•
Electrical power.
•
Check area around boiler. Remove any combustible materials, gasoline
and other flammable liquids.
Top View
Walls
Floor
Ceiling
Wall
Figure 3
Recommended service clearances
Provide clearances around boiler
(see Figure 3)
Jacket cap must be in place on boiler to
avoid requiring an 9" minimum clearance
from back or top of boiler to combustible
material.
•
MINIMUM clearances from vent pipe to combus-
tible material:
•
6 inches — Type “L” double-wall vent
•
9 inches — Single-wall vent
Flue pipe clearances must take precedence
over jacket clearances.
•
Recommended SERVICE clearances:
•
24 inches — Front and top
•
6 inches — Left side, back and right side
•
15 inches — Left side with tankless heater
•
12 inches — Right side for burner door swing
radius
24"
C
A
B
D
D
D
24"
Before installing boiler
A
Provide 6" minimum clearance for service, provide 12" minimum clearance for
burner door swing.
B
Provide 6" minimum clearance for service.
C
Provide 6" minimum clearance for service, provide 15" left side with tankless heater.
D
Minimum clearance from vent pipe to combustible material: 6" for type “L” double-
wall vent, 9" for single-wall vent.
Failure to keep boiler area clear and free of combustible materials, gasoline and other flammable liquids and vapors
can result in severe personal injury, death or substantial property damage.
Part number 550-141-829/1211
9
GOLD
SGO
OIL-FIRED NATURAL DRAFT STEAM BOILER — SERIES 3 —
Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.
Homeowner — STOP!
The procedures and information on this and following pages are intended only for a quali-
fied service technician who has the necessary equipment to inspect and adjust boiler and burner. A homeowner
should never attempt these procedures. The service technician must also read pages 1 through 8 before proceeding.