WI-GTWY-9-xxx Wireless Gateway V1.18
52
For each “remote input” configured to a WI-GTWY-9-xxx, there is a comms-fail time parameter
in the WI-GTWY-9-xxx. If the WI-GTWY-9-xxx does not receive a message destined to that
I/O register within the “comms fail” time, then the “comms fail” status for that I/O register will
be set - the most significant bit of the status register will be set to 1. The comms fail time
should be more than the corresponding update time at the remote input.
To set the comms fail times, select the WI-GTWY-9-xxx, and select the “Comms Fail Time”
option. Each remote input already mapped to the WI-GTWY-9-xxx will automatically be listed,
including the remote module containing the mapping.
The default value for the
comms-fail time is “disabled”
or zero. To enter a time,
select the I/O register from the
list. The comms-fail time
should be greater than the
update time of the remote
input.
Firmware version 1.76 and later:
The I/O value in the I/O registers can be reset to zero on comms-fail. To enable this, select the
enable box in the “Comms Fail Times” configuration screen. Note that this is a global selection;
comms-fail-reset is configured on all registers or no registers.
4.4.2
Mappings from WI-GTWY-9-xxx to Outputs at Remote WI-I/O 9-x I/O Modules
Mappings can be entered in the WI-GTWY-9-xxx to remote outputs. Select the “Mappings”
option under the WI-GTWY-9-xxx. Select an I/O register and select the remote module and the
output channel.
To map several consecutive I/O registers to several outputs, select the first I/O register in the
range and use “Shift”-select or “Ctrl” - select to highlight the multiple outputs. The selected
mappings will be entered with consecutive I/O registers.