WI-GTWY-9-xxx Wireless Gateway V1.18
159
To check firmware version
1.
Start W-Series Configuration Utility and open up the appropriate project.
2.
Select from the module you wish to monitor comms at.
3.
Press the “Diagnostic” button on the right hand side of the configuration screen and a new
window will open headed “Communications Log”.
4.
Hold down the indented black button (on the end of the module) until the ACT LED
flashes (about 5 seconds), release button and you should now see “Type ‘m’ for
menu......” press “m” and a Configuration Menu will appear.