Profibus Slave Indicating LED’s
LED No
Indication
Description
1
-
Not Used
2
Green
Module is On-Line and data exchange is possible.
2
Off
Module is not On-Line
3
Red
Module is Off-Line and no data exchange is possible.
3
Off
Module is not Off-Line
4
Flashing Red 1
Hz
Error in configuration: IN and/or OUT length set during
initialization of the module is not equal to the length set during
configuration of the network.
4
Flashing Red 2
Hz
Error in User Parameter data: The length/contents of the User
Parameter data set during initialization of the module is not equal
to the length/contents set during configuration of the network.
4
Flashing Red 4
Hz
Error in initialization of the Profibus communication ASIC.
4
Off
No diagnostics present