Parameters Description
Crane | 27
3.1.1 Configuration of the Commands
This parameter group allows the user to configure some of the CFW500 frequency inverter commands,
necessary for the crane application.
P0229 – Stop Mode Selection
Adjustable
0 = Ramp to Stop
Factory Setting:
0
Range:
1 = Coast to Stop
2 = Fast Stop
Proprieties:
Access groups via HMI:
BASIC
Description:
This parameter defines the motor stop mode when the inverter receives the “Stop” command.
NOTE!
Refer to the CFW500 programming manual for more information on the stop mode.
P1024 – Enable use of a Filter in the Hoisting/Forward and Lowering/Reverse Commands
Adjustable
0.00 to 15.00 s
Factory Setting:
0.10 s
Range:
Proprieties:
Access groups via HMI:
SPLC
Description:
This parameter enables the use of a time as a filter to accept the load hoisting/forward and load
lowering/reverse commands via the digital inputs DI1 and DI2 or communication network to prevent too fast or
false commands are accepted by the crane vertical or horizontal motion.
With the value in “0.00 s” (disabled), there is no filter on the digital inputs DI1 and DI2.
With the value different of “0.00 s” (enabled), a filter is applied to the load hoisting/forward and load
lowering/reverse commands in changing the logic state "0" to "1".
P1026 – Motor Rotation Direction Inversion
Adjustable
0 = Off
Factory Setting:
0
Range:
1 = On
Proprieties:
CFG
Access groups via HMI:
SPLC
Description:
This parameter inverts the motor rotation direction that is normally adopted for the load hoisting/forward and
load lowering/reverse commands.
With the option "0" (Disabled), the load hoisting/forward command occurs with forward rotation direction and
the load lowering/reverse command with reverse rotation direction.
With the option "1" (Enabled), the load hoisting/forward command occurs with reverse rotation direction and the
load lowering/reverse command with forward rotation direction.
P1027 – Motor Demagnetization Time
Adjustable
0 to 65000 s
Factory Setting:
600 s
Range:
Proprieties:
Access groups via HMI:
SPLC