Parameterization
SRW 01 | 5-13
5
Table 5.5:
Configuration of the digital inputs and outputs for the Transparent operation mode
Digital Inputs /Outputs
Function
I11
Free
I12
Free
I13
Free
I14
Free
I15
Free
I16
Free
O1
Ladder
O2
Ladder
O3
Ladder
O4
Ladder
ATTENTION!
If either error or Trip occurs in the Transparent mode, the Control Unit (UC) will not automatically Switch
Off its outputs. Protections must be programmed by the user with the error or Trip bits in the Ladder
logic of the Control Unit (UC).
5.4.2.1 Connection Diagram – Transparent Mode
shows an example of the use of the Control Unit (UC) on the Transparent
operation mode with drive through the digital inputs at 24 Vdc, where on the Ladder programming digital input
I11 turns the motor on/off, digital input I12 is used as a Check Back signal and digital output O1 drives the motor.
A2
A2
A1
A1
IC
I16
I15
I14
I13
I12
I11
K1
K1
S0
K1
1
2
L1
T1
U
3
4
L2
T2
V
M
3
~
5
6
L3
T3
W
Q1
Q1
Q2
C1
C3
C4
01
03
04
02
SRW01-UC
R/L1
R/L1
S/L2
T/L3
N
110...240 VAC/VDC 50/60Hz
SRW01-UMC
SRW01-CB
Figure 5.2:
Connection scheme for the Transparent operation mode using digital inputs at 24 Vdc
5.4.3 Overload Relay
In this operation mode the Control Unit (UC) presents operation characteristics similar to an Overload Relay, using
one NO (normally open) digital output and another NC (normally closed). The other digital outputs can be used
according to the user’s needs.