WDT Operating instructions GRANUDOS 10 (V61-08/05) page 12 of 20
____________________________________________________________________________
Diagram for the Determination of the Switch Positions for the Cycle and Dosing Time
Table for Cycle amd Dosing Times
Switch
Cycle Time
Dosing Time
Position
Chlorine Acid
Sec. %
Sec. %
Sec. %
1
439 6
0,5 3
0,5 6
2
411 8
1 6
1 13
3
342 9
1,5 9
1,5 19
4
285 11
2 13
2 25
5
238 13
2,5 16
2,5 31
6
198 16
3 19
3 38
7
165 19
3,5 22
3,5 44
8
138 23
4 25
4 50
9
115 28
5 31
4,5 56
10
95 34
6 38
5 63
11
80 40
7,5 47
5,5 69
12
66 48
9 56
6 75
13
55 58
10,5 66
6,5 81
14
46 69
12 75
7 88
15
38 84
14 88
7,5 94
16
32 100
16
100
8 100
The percentage values of the performance table are to be related to the maximum dosing rates:
GRANUDOS 10: Chlorine app. 1. kg/h. acid app. 2 1/
Cycle Time
Dosing Performance
Dosing Time
Acid Chlorine