WIRING DIRECTIONS
Each WattStopper B series power pack can supply power for up to 2 DT-200
sensors. Each WattStopper BZ series power pack can supply power for 3 DT-200
sensors. When using more sensors than this, multiple power packs are required.
Refer to the wiring diagram on the next page for the following procedures:
Connect the
LOW VOLTAGE
:
• RED wire (+24VDC) from power pack to the
violet
wire on the sensor.
• BLACK wire (Return) from power pack to the
gray
wire on the sensor.
Wiring a
SINGLE LIGHTING LOAD CONTROLLED BY OCCUPANCY
– connect:
• BLUE wire from power pack to the
yellow
wire on the sensor.
To add a
MOMENTARY MANUAL SWITCH
such as the LVS-1 Momentary Toggle
Switch, to the above applications–connect:
• Wire from one side of switch to the
green
wire on sensor.
• Wire from other side of switch to the
gray
wire on sensor.
Wiring the
ISOLATED RELAY
: (The Isolated Relay is rated for 1A@30VAC/VDC)
Connect the wires necessary to the application that requires this output:
• Relay Common (must be used for proper operation) is the
red
wire
• N.O. (Normally Open)–Closed when occupancy is detected, is the
orange
wire
• N.C. (Normally Closed)–Open when occupancy is detected, is the
brown
wire
CAUTION
TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE
INSTALLING POWER PACKS OR SENSORS.
Call 800.879.8585 for Technical Support