background image

14

6. Other Features

6.1 Anti Grip Feature

The feature is enable using DIP6 (See 3.3). If the valves are not active during a week, a complete exercise is triggered 
(ac pump o Heat/cool demand sent to the WFC-03 HCM RF 230).

6.2 Reset

In case of dysfunction, it may be required to reset the product to factory setting. By pressing 

 for 5 seconds, the master 

goes in Reset menu.
Then by pressing simultaneously on 

 , 

 and 

 up to getting all zone LED in red, the controller reset is triggered and the 

product restarts.

6.3 Trouble shooting

Open even actuators

Exercice start

Close odd actuators

Open odd actuators / Close even actuators

Start pump

at 2min or 5min

if not ever activated

Exercice end

5min

5min

Symptom #

Trouble

Description

Trouble shooting

Red or blue blinking 
on Heat and Cool led.
And Red blinking on 
Pump/Drier Led.

Security 
detection.

The contact of the security input 
is opened.

If you not using a security thermostat, make 
sure, you have installed a strap on the security 
thermostat input.
Otherwise control the temperature of the pipe 
(too hot in heating mode, too cold in cooling 
mode).

Red / Blue blinking on 
Heat and Cool led.

RF Issue.

The controller has lost the 
connection with a RF device 
other than a thermostat.

Check distance between devices. If the 
controller is installed within a metallic box, 
use an external antenna located outside the 
metallic box. 
A RF repeater may be required.

Fast Blue flashing on 
Pump/Drier Led.

Humidity 
configuration 
problem

CTN measurement on H&C 
input whereas the DIP8 = OFF.
ON/OFF input on H&C input 
whereas the DIP8 = ON.

Check CTN and DIP switch setting

Red blinking on 1 
zone.

RF error with the 
thermostat.

The controller has lost the 
connection with the thermostat.

Check distance between the controller and the 
thermostat.
A RF repeater may be required.

Red blinking on all 
zones.

RF antenna 
error.

The controller has lost all RF 
connections (Thermostat and 
other devices).

External antenna may be required.

Содержание WFC-03 6Z HC RF 24

Страница 1: ...wattswater fr WFC 03 6Z HC RF 24 WFC 03 6Z HC RF 230 WFC 03 10Z HC RF 24 WFC 03 10Z HC RF 230 Water Floor Controller Wireless Heating Cooling Installation manual...

Страница 2: ...nfiguration 5 USB stick 5 INPUTS OUTPUTS 6 Power Supply 6 Heating cooling Input 6 Pump Output 7 Security input 7 Humidity detection input 8 NC NO actuators 9 External antenna 9 SYSTEM CONFIGURATION 10...

Страница 3: ...ith existing regulations before operation to ensure proper use of the installation 2 Presentation The Connecting box WFC HC RF is especially designed to control your Under Floor Heating and Cooling sy...

Страница 4: ...the system switches in Heating mode Pump Drier Led Green Blue Red Fix Green Pump is triggered Red blinking System error security detection humidity sensor error Blue blinking Global humidity detection...

Страница 5: ...the Software of the controller To record data for system monitoring datalog For the software update please refer to wattswater eu for getting the file put the file on an USB stick The name of the fil...

Страница 6: ...ostat in manual or automatic mode only one thermostat per installation If you have multiple WFC 03 HC RF in the system the H C mode should be controlled by only one controller Without central the syst...

Страница 7: ...rity input should be used on a controller with a pump When the contact is opened The local pump output is stopped even if DIP1 ON i e global pump on the controller The actuators are closed The Pump Dr...

Страница 8: ...module WFC 03 HCM RF to enable the global dehumidifier for at least 15min and up the disappearance of the alarm if no remote dehumidifier is available in the zone If the controller is a sub controlle...

Страница 9: ...ation Many heat pumps have a built in turn off delay to avoid successive switch OFF ON In this case the heat pump continues to run for x minutes beyond the actual switch off time It is important to ke...

Страница 10: ...sition indicator Already paired zone is fix green Thermostats Put product in RF pairung mode refer to corresponding instruction manual If RF pairing is done the LEDs of the zones selected on the WFC 0...

Страница 11: ...03 HC RF BT WR02 RF Option WFC 03 HCM RF 230 Option BT A03 RF Device 1 Device 2 Remarks By pressing for 5 seconds the controller goes in RF pairing menu By using and select zone 3 Red led press to en...

Страница 12: ...vice mode All LEDs are blinking red When RF pairing is done both WFC 03 HC RF return to pairing mode Exit of the controller pairing menu Long press on Device 1 WFC 03 HC RF Device 2 BT CT02 RF Remarks...

Страница 13: ...oes in RF pairing menu By using and select zone 4 Red blinking led press to enter in dehumidifier Pairing mode Choose the zones with and Zones are defined by paired thermostat channels For example if...

Страница 14: ...y input is opened If you not using a security thermostat make sure you have installed a strap on the security thermostat input Otherwise control the temperature of the pipe too hot in heating mode too...

Страница 15: ...WFC 03 10Z HC RF 24 WFC 03 10Z HC RF 230 Electrical protection Class II with functional earth IP Protection IP30 Shipping and storage temperature 10 C to 50 C 14 F to 122 F Power supply 230 Vac 10 50H...

Страница 16: ...ectromagnetic disturbance 2014 30 UE Restriction of the use of certain hazardous substances Directive RoHS 2011 65 EU Directive on the restriction of the use of certain hazardous substances in electri...

Страница 17: ...ion sheet are supplied by way of information only and are not binding Watts Industries reserves the right to carry out any technical and design improvements to its products without prior notice Warran...

Отзывы: