22
Settings (5 of 5)
Parameter
Range
Description
ALERTS
BOILER PLANT
NO HEAT ALERT
ENABLE
Off or On
Default: Off
Select if an alert is triggered if the condensate return temperature does not increase .
Requires a condensate sensor to be installed .
BOILER PLANT NO
HEAT ALERT
5 .0 to 80 .0 minutes
Default: 60 .0 minutes
Set the amount of time of no temperature change while boilers are firing after which
the control triggers a boiler plant no heat alert notification . Requires a condensate
sensor to be installed .
HIGH PRESSURE
ALERT
0 .0 to 15 .0 psi
(0 to 105 kPa)
Default: 15 .0 psi
(105 kPa)
Set the threshold above which the control triggers a high pressure alert notification .
FLUE
TEMPERATURE
ALERT
100 to 392°F
(38 .0 to 200 .0°C)
Default: 392°F (200 .0°C)
Set the threshold above which the control triggers a flue temperature alert notification .
INDOOR
TEMPERATURE
COLD ALERT
ENABLE
Off or On
Default: Off
Select if an alert is triggered if the indoor temperature falls below the threshold .
Requires an indoor sensor to be installed .
INDOOR
TEMPERATURE
COLD ALERT
32 to 100°F
(0 .0 to 38 .0 °C)
Default: 38°F (3 .5°C)
Set the threshold below which the control triggers an indoor temperature cold alert
notification . Requires an indoor sensor to be installed .
INDOOR
TEMPERATURE HOT
ALERT ENABLE
Off or On
Default: Off
Select if an alert is triggered if the indoor temperature exceeds the threshold . Requires
an indoor sensor to be installed .
INDOOR
TEMPERATURE HOT
ALERT
32 to 100°F
(0 .0 to 38 .0 °C)
Default: 78°F (25 .5°C)
Set the threshold below which the control triggers an indoor temperature hot alert
notification . Requires an indoor sensor to be installed .
BOILER 1 SERVICE
HOURS ALERT
1000 to 25000 hours
Default: 5000 hours
Set the number of boiler running hours above which the control triggers a boiler
service alert notification .
BOILER 1 SERVICE
CYCLES ALERT
1 to 25000 cycles
Default: 25000 cycles
Set the number of boiler on/off cycles above which the control triggers a boiler
service alert notification .
BOILER 2 SERVICE
HOURS ALERT
1000 to 25000 hours
Default: 5000 hours
Set the number of boiler running hours above which the control triggers a boiler
service alert notification .
BOILER 2 SERVICE
CYCLES ALERT
1 to 25000 cycles
Default: 25000 cycles
Set the number of boiler on/off cycles above which the control triggers a boiler
service alert notification .
SECURITY
STEP 1
N/A
Set a personal passcode . This is required when a passcode has already been set .
STEP 2
N/A
Confirm the personal passcode . This is required when a passcode has already
been set .
REQUIRE
PASSCODE
Off or On
Default: Off
Select if a passcode is required to enter the Home screen .
PASSCODE
N/A
Select to change the personal passcode . Redirects user to Steps 1 and 2 .