Parameter
Range
Description
STAGING STATUS
SYSTEM
0 .0 to 15 .0 psi
(0 to 105 kPa)
The system steam pressure .
TARGET
1 .0 to 15 .0 psi
(0 to 105 kPa)
The pressure that shuts off the second boiler .
DIFFERENTIAL
0 .1 to 5 .0 psi
(7 to 35 .0 kPa)
The pressure below the target to turn on the second boiler .
STAGE DELAY
0 .0 to 40 .0
minutes
The time delay must elapse to 0 .0 to turn on the second boiler .
BOILER STATUS
BOILER 1 OR 2
HOURS
0 to 999999
hours
The number of hours the boiler has fired .
BOILER 1 OR 2
CYCLES
0 to 999999
cycles
The number of boiler on/off cycles .
Settings (1 of 5)
Parameter
Range
Description
UNITS
TEMPERATURE
°F or °C
Default: °F
Units for display of temperature .
PRESSURE
psi or kPa
Default: psi
Units for display of pressure .
DATE AND TIME
24-HOUR TIME
Off or On
Default: Off
Selects a 24 hour time clock .
SET
AUTOMATICALLY
Off or On
Default: On
Automatic synchronizes the time with the Internet .
TIME ZONE
North American Time
Zones
Default: Eastern
Select from Newfoundland, Atlantic, Eastern, Central, Mountain, Pacific, Alaska,
Hawaii time zones .
DATE
Month, Day, Year
Set the current date . Available when setting time manually .
TIME
Hours, Minutes, AM/PM Set the current time . Available when setting time manually .
DAYLIGHT
SAVINGS
Off or On
Default: On
Select if daylight savings time is locally observed .
INTERNET
CONNECTION
TYPE
Off, Ethernet, Wi-Fi
Default: Off
Select the Internet connection .
WI-FI NETWORK
Scans for all available
networks
Select the desired Wi-Fi network SSID . Then enter the Wi-Fi password .
WI-FI SECURITY
TYPE
None, WPA2-Personal,
WPA2-Enterprise
Default: WPA2-Personal
Select the type of Wi-Fi security . WPA2-Enterprise requires a RADIUS authentication
server using PEAPv0/EAP-MSCHAPv2 . This is available when setting the
Wi-Fi manually .
WI-FI USER
32 character name
User the WPA2-Enterprise user name . Available when configuring Wi-Fi to use
WPA2-Enterprise .