© 2020 tekmar 087_D - 02/20
Resistance
Temperature
336095
-40°F (-40°C)
242426
-31°F (-35°C)
176801
-22°F (-30°C)
130307
-13°F (-25°C)
97007
-4°F (-20°C)
72910
5°F (-15°C)
55303
14°F (-10°C)
Resistance
Temperature
42316
23°F (-5°C)
32651
32°F (0°C)
25395
41°F (5°C)
19903
50°F (10°C)
15714
59°F (15°C)
12493
68°F (20°C)
10000
77°F (25°C)
Resistance
Temperature
8056
86°F (30°C)
6530
95°F (35°C)
5325
104°F (40°C)
4367
113°F (45°C)
3601
122°F (50°C)
2985
131°F (55°C)
2487
140°F (60°C)
10K Type 2 NTC Thermistor (tekmar)
ON
Resistance
Temperature
239686
-40°F (-40°C)
179200
-31°F (-35°C)
135185
-22°F (-30°C)
102861
-13°F (-25°C)
78913
-4°F (-20°C)
61020
5°F (-15°C)
47543
14°F (-10°C)
Resistance
Temperature
37313
23°F (-5°C)
29490
32°F (0°C)
23457
41°F (5°C)
18780
50°F (10°C)
15130
59°F (15°C)
12263
68°F (20°C)
10000
77°F (25°C)
Resistance
Temperature
8194
86°F (30°C)
6752
95°F (35°C)
5592
104°F (40°C)
4655
113°F (45°C)
3893
122°F (50°C)
3271
131°F (55°C)
2760
140°F (60°C)
10K Type 3 NTC Thermistor
ON
Sensor Resistance Settings
DIP switches in the right side of the wiring chamber are configured to match the
sensor requirements of the connected control. See below for equipment compatibility:
Setting
Boilers
Controls
5k
• Viessmann Vitodens-100W WB1B
• Heat Timer (excl. EPU-CH)
10k Type 2
• Laars Mascot
• Laars Neotherm
• Viessmann
models after 2012
(incl. Vitodens 100W
B1HA & B1KA, 200
B2HA & B2HB,
222 B2TA & B2TB,
Vitocrossal 300
CU3A)
• Lochinvar
• Allied SG, AAA and
Electric
• IBC SL,VFC
• Slant/Fin CHS
• NTI Trinity & Vmax
• Raypak
• RBI
• Smith Boiler
• ATH
• Navien
• Camus
• tekmar reset controls
and thermostats
• Honeywell AQ2000
• Uponor CCN
10k Type 3 • Buderus GB Series
• Taco iWorx
12k
• Peerless Purefire
• IBC DC & HC
Series
• Triangle Tube
Prestige Solo &
ACVMax
• HTP Elite
• Allied HSE
• Bosch Greenstar
• Weil-McLain Ultra
Series 3, Evergreen
& 97+
• Slant/Fin Lynx
• Slant/Fin Jaguar
20k
• Honeywell Building Controls