10 of 20
8. Follow the instructions provided with the sensor to
connect them to the tekmar snow melting control.
Refer to the corresponding tekmar installation manual
for further information on wiring.
For a ProMelt panel to operate properly, either an 090 or
095 snow melt sensor and Outdoor Sensor 070 must be
installed and wired to the panel.
Slab
Conduit
Sensor
Rebar Anchor
Installation
This manual does not detail how to install external
sensors. For details on how to install the sensors and
socket, please refer to installation manuals included with
the sensor packaging.
NOTICE
ALL CONDUIT AND RELATED ACCESSORIES MUST
BE INSTALLED PRIOR TO SENSOR INSTALL.
Use five-conductor 18 AWG LVT cable for the 090 or 095
sensor and two-conductor 18 AWG LVT cable for
the 070 air sensor. Either cable can be run up to 500 feet
without impacting performance. Contact the factory if a
longer distance is required.
Sensors are not pre-wired to the ProMelt Panel. The
tekmar Snow / Ice Sensor 090 comes with 65 feet of the
necessary 18 AWG cable.
Blu Yel Brn/
Slab
Blk/
Com
Red
Mod
Enable
T
T
+
-
Mod Boiler Boiler 1
Stage 1
–
+
Stage 1
T
T
Boiler 1
Stage 1
Com Boil Out
090
Snow Sensor
Modulating
Boiler