All configurations must include manifold vent/purge
assemblies. Failure to do so may result in complications
purging.
NOTICE
15. Use the tekmar control to enable the system pump
relay and allow remaining air to circulate through to
the vents.
Using the touch screen on the tekmar control, navi-
gate to Settings, Override, and select Manual Override.
Change this to “Hand”. Select Back, then arrow down to
System Pump and select “On”.
The control defaults to a run time of 10 minutes. If a lon-
ger manual run time is needed, go to the Override screen
and arrow down to select “Hand Duration”. Enter the
desired run time.
1. Home Screen: Select Settings
2. Select Override
3. Select Manual Override
4. Select Hand type and
then Back
5. Select System Pump
6. Select On then Back
7. Arrow down to Select Hand
Duration to modify run times
16. Allow pumps to run until air has been vented.
17. Turn off pumps and fill system to 15 psi. This may
need to be done several times as air will vent over
the next few days.
18. Close D1 and disconnect hose.
19. Manually enable system pump relay again, and ad-
just V4 to achieve desired flow.
20. Ensure caps are placed tightly on drain valves and
return the valves to open positions.
For additional information on setting up the control, refer
to the enclosed tekmar control literature.
System Commissioning and Maintenance