ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX D: EIGHT C-MORE BOILERS/HEATERS AND BST/WHM MASTER
OMM-0150_B
• 5/20/2021 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
97
of
140
Appendix D: Eight C-More Boilers/Heaters and BST/WHM Master
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2
ID
Lon NAME Lon SNVT Lon Direction
Modbus
Address
8
Run Hours Upper
SMD_BAS_IP_HTR_08_[17]
✓
AV:1017
Data Float
203
nvoHTR_08_18 inc count (9)
Output (non-polled)
31017
8
Run Hours Lower
SMD_BAS_IP_HTR_08_[18]
✓
AV:1018
Data Float
204
nvoHTR_08_19
inc count (9)
Output (non-polled)
31018
8
Oxygen Level
SMD_BAS_IP_HTR_08_[19]
✓
AV:1019
Data Float
205
nvoHTR_08_20
inc count (9)
Output (non-polled)
31019
Appendix D: Eight C-More Boilers/Heaters and BST/WHM Master
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2
ID
Lon NAME Lon SNVT Lon Direction
Modbus
Address
Blr Addr 9
9
Comm Address
SMD_BAS_IP_HTR_09_[0]
✓
AV:1100
Data Float
206
nvoHTR_09_1 inc count (9)
Output (non-polled)
31100
9
Unit Status
SMD_BAS_IP_HTR_09_[1]
✓
AV:1101
Data Float
207
nvoHTR_09_2 inc count (9)
Output (non-polled)
31101
9
Fault Code
SMD_BAS_IP_HTR_09_[2]
✓
AV:1102
Data Float
208
nvoHTR_09_3 inc count (9)
Output (non-polled)
31102
9
Outlet Temp
SMD_BAS_IP_HTR_09_[3]
✓
AV:1103
Data Float
209
nvoHTR_09_4 inc count (9)
Output (non-polled)
31103
9
FFWD Temp
SMD_BAS_IP_HTR_09_[4]
✓
AV:1104
Data Float
210
nvoHTR_09_5 inc count (9)
Output (non-polled)
31104
9
Inlet Temp
SMD_BAS_IP_HTR_09_[5]
✓
AV:1105
Data Float
211
nvoHTR_09_6 inc count (9)
Output (non-polled)
31105
9
Exhaust Temp
SMD_BAS_IP_HTR_09_[6]
✓
AV:1106
Data Float
212
nvoHTR_09_7 inc count (9)
Output (non-polled)
31106
9
Air Temp
SMD_BAS_IP_HTR_09_[7]
✓
AV:1107
Data Float
213
nvoHTR_09_8 inc count (9)
Output (non-polled)
31107
9
Flame Strength
SMD_BAS_IP_HTR_09_[8]
✓
AV:1108
Data Float
214
nvoHTR_09_9 inc count (9)
Output (non-polled)
31108
9
Fire Rate In
SMD_BAS_IP_HTR_09_[9]
✓
AV:1109
Data Float
215
nvoHTR_09_10 inc count (9)
Output (non-polled)
31109
9
Fire Rate Out
SMD_BAS_IP_HTR_09_[10]
✓
AV:1110
Data Float
216
nvoHTR_09_11 inc count (9)
Output (non-polled)
31110
9
Unit Type
SMD_BAS_IP_HTR_09_[11]
✓
AV:1111
Data Float
217
nvoHTR_09_12 inc count (9)
Output (non-polled)
31111
9
Unit Size
SMD_BAS_IP_HTR_09_[12]
✓
AV:1112
Data Float
218
nvoHTR_09_13 inc count (9)
Output (non-polled)
31112
9
Value State
SMD_BAS_IP_HTR_09_[13]
✓
AV:1113
Data Float
219
nvoHTR_09_14 inc count (9)
Output (non-polled)
31113
9
Net Remote Setpt
SMD_BAS_IP_HTR_09_[14]
✓
AV:1114
Data Float
220
nvoHTR_09_15 inc count (9)
Output (non-polled)
31114
9
Run Cycles Upper
SMD_BAS_IP_HTR_09_[15]
✓
AV:1115
Data Float
221
nvoHTR_09_16 inc count (9)
Output (non-polled)
31115