ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX C: AERCO EQUIPMENT POINT MAPPINGS
OMM-0150_B
• 5/20/2021 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
85
of
140
Point Name
FPC-N34
FPC-N35
Modbus
Address
BACnet
Data Type
BACnet
Object Id
N2 Data
Type
N2 Point
Address
Lon Name
Lon SNVT Type
Current Lockout Error
diagnostics
AI
122
AI
122
nvoCrLkErDig_XXX
SNVT_count_inc_f
40402
Current Lockout Error class
AI
123
AI
123
nvoCrLkErCls_XXX
SNVT_count_inc_f
40403
Current Lockout Error phase
AI
124
AI
124
nvoCrLkErPhs_XXX
SNVT_count_inc_f
40404
Current Lockout Fuel
AI
125
AI
125
nvoCrLkFuel_XXX
SNVT_count_inc_f
40405
Current Lockout Output
AI
126
AI
126
nvoCrLkOutpt_XXX
SNVT_count_inc_f
40406
Current Lockout Date: Year
AI
127
AI
127
nvoCrLkDtYr_XXX
SNVT_count_inc_f
40407
Current Lockout Date: Month
AI
128
AI
128
nvoCrLkDtMnt_XXX
SNVT_count_inc_f
40408
Current Lockout Date: Day
AI
129
AI
129
nvoCrLkDtDay_XXX
SNVT_count_inc_f
40409
Current Lockout Time of day:
Hours
AI
130
AI
130
nvoCrLkTmHrs_XXX
SNVT_count_inc_f
40410
Current Lockout Time of day:
Minutes
AI
131
AI
131
nvoCrLkTmMin_XXX
SNVT_count_inc_f
40411
Current Lockout Time of day:
Seconds
AI
132
AI
132
nvoCrLkTmSec_XXX
SNVT_count_inc_f
40412
Current Lockout Startup
counter total
AI
133
AI
133
nvoCrLkCtTot_XXX
SNVT_count_inc_f
40413
Current Lockout Hours run
total
AI
134
AI
134
nvoCrLkHrRnT_XXX
SNVT_time_hour
40415
Current Error Error code
AI
135
AI
135
nvoCrErCode_XXX
SNVT_count_inc_f
40545
Current Error Error diagnostics
AI
136
AI
136
nvoCrErDiag_XXX
SNVT_count_inc_f
40546
Current Error Error class
AI
137
AI
137
nvoCrErClass_XXX
SNVT_count_inc_f
40547
Current Error Error phase
AI
138
AI
138
nvoCrErPhase_XXX
SNVT_count_inc_f
40548
Current Error Fuel
AI
139
AI
139
nvoCrErFuel_XXX
SNVT_count_inc_f
40549
Current Error Output
AI
140
AI
140
nvoCrErOutpt_XXX
SNVT_count_inc_f
40550
Current Error Startup Counter
Total
AI
141
AI
141
nvoCrErCtrTo_XXX
SNVT_count_inc_f
40551