ProtoNode FPC-N34 & FPC-N35 User Manual
CHAPTER 8
– LonWorks (FPC-N35) Commissioning ProtoNode
OMM-0150_B
• 5/20/2021 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
45
of
140
CHAPTER 8.
LONWORKS (FPC-N35): COMMISSIONING
PROTONODE ON A LONWORKS NETWORK
Commissioning may only be performed by the LonWorks administrator.
8.1 Commissioning ProtoNode FPC-N35 on a LonWorks Network
The User will be prompted by the LonWorks Administrator to hit the Service Pin on the
ProtoNode FPC-N35 at the correct step of the Commissioning process which is different for
each LonWorks Network Management Tool.
•
If an XIF file is required, see steps in Section 8.1.1 to generate XIF.
Figure 8-1: LonWorks Service Pin Location
8.1.1 Instructions for Downloading XIF File from ProtoNode FPC-N35 Using
Browser
•
Connect a CAT5 Ethernet cable (Straight through or Cross-Over) between the PC and
ProtoNode.
•
The Default IP Address of ProtoNode is
192.168.1.24
, Subnet Mask is
255.255.255.0
. If
the PC and ProtoNode are on different IP Networks, assign a static IP Address to the PC
on the 192.168.1.xxx network.
•
For Windows XP:
1. Click
, choose
Control Panel
, and then choose
Network
Connections
.
2. Right-click on
Local Area Connection > Properties
.
3. Highlight
>
•
For Windows 7:
1. Click
and choose
Control Panel.