Benchmark Platinum-Edge [ii]: Installation Manual
SECTION 2
– INSTALLATION
OMM-
136_E • GF
-210
•
12/13/2019
Technical Support
• (
800) 526-0288
• Mon
-Fri, 8 am - 5 pm EST Page 29 of 57
NOTE:
It is the responsibility of the customer to source and purchase the appropriate gas regulator
as described above. However, AERCO offers for sale an appropriate regulator, which may
be ordered at the time of unit purchase or separately. Contact your AERCO sales
representative for more information.
On all Benchmark models it is strongly recommended that the pressure regulator be installed a
minimum distance of 10 pipe diameters between the pressure regulator and the nearest
downstream
fittings (an elbow or the unit itself), and a minimum of 5 pipe diameters between the
pressure regulator and any
upstream
fitting, such as elbow or shutoff valve, as shown in Figure
2-7a, below (this recommendation applies to, but is not shown, in Figures 2-7b
–2-7d).
Figure 2-7a: BMK750/1000 Gas Regulator and Manual Shut-Off Valve
1” MANUAL
SHUTOFF VALVE
GAS PRESSURE
REGULATOR
DIRT LEG
GAS INLET
MINIMUM 10 PIPE
DIAMETERS IN
LENGTH
MINIMUM 5 PIPE
DIAMETERS IN
LENGTH