Benchmark Platinum-Edge [ii]: Installation Manual
SECTION 2
– INSTALLATION
OMM-
136_E • GF
-210
•
12/13/2019
Technical Support
• (
800) 526-0288
• Mon
-Fri, 8 am - 5 pm EST Page 43 of 57
Sequencing Isolation Valve Installation Instructions
Figure 2-13: Sequencing Isolation Valve Installed
2. Find the grey cable insid
e the unit’s enclosure with the unused Molex connector with a cap
containing a jumper wire inserted in it (the jumper wire allows units that do not have a
sequencing isolation valve to operate normally). The other end is connected to the I/O
board and to a power supply.
Figure 2-14: Sequencing Isolation Valve Molex Connector and Jumper Wire
Isolation Valve Harness
Wire #
Color
Signal
1236
Black
24V Common
1237
Red
24V Hot
1238
White
Valve analog input
1239
Green
Valve analog feedback
1240
Black
Delayed interlock
1241
Black
3. Remove and dispose of the cap with jumper wire attached.
4.
Plug the Molex connector into the sequencing isolation valve’s connector.
5.
When the Sequencing Isolation Valve is used, the Controller’s
Auxiliary Delay
setting
mu
st be set to 120 seconds. Go into the Controller’s
Main Menu
→
Advanced Setup
→
Ancillary Device
→
Interlocks
screen, and set the
Auxiliary Delay
setting to
120
.
HOT WATER
OUTLET
AERCO
SEQUENCING
ISOLATION
VALVE
MOLEX CONNECTOR
JUMPER
CAP