Benchmark Platinum-Edge [ii]: Installation Manual
SECTION 3
– ONAER SETUP
OMM-
136_E • GF
-210
•
12/13/2019
Technical Support
• (
800) 526-0288
• Mon
-Fri, 8 am - 5 pm EST Page 44 of 57
2.15 BOILER PUMP RELAY
Figure 2-15: Boiler Pump Relay
The Benchmark Platinum
’s power panel includes a secondary output board with a pump relay
that is designed to operate a boiler pump. This relay provides 120VAC with a maximum pilot
duty of 3 amps. If the pump power requirement under all conditions is greater than 3 amps, it is
required to use this relay to activate the pump through an intermediate relay with a higher
power.