Benchmark 5000-6000 Operation & Maintenance Manual
APPENDIX A: BOILER MENU DESCRIPTIONS
OMM-0118_B
•
GF-203
•
5/9/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 92 of 148
TABLE A-1: OPERATING Menu Item Descriptions
MENU OPTIONS
DESCRIPTION
16
Air Pump Voltage
A voltage signal proportional to the current drawn by the Air
Eductor
’s Air Pump. This pump draws a sample of gas across the
O
2
sensor anytime the boiler has proven flame operation.
If Air Pump voltage is less than 0.20V or greater than 1.20V for
more than 10 seconds, a
AIR PUMP FAILED / O2 TRIM
DISABLED
message is generated. It can only be cleared by
pressing the
CLEAR
button on C-More Controller.
17
Run Cycles
Displays the total number of run cycles.
18
Run Hours
Displays total run time of unit in hours.
19
Fault Log
Displays information on the last 20 faults.
20
Manual Valve Pos
Selects valve position. Available in
Manual mode
only!